R-410A vs R-32

Reviewed · pressures computed with CoolProp 8.0 from the same data as the PT charts

Can you put R-32 in an R-410A system?

No. R-32 is an A2L (mildly flammable) refrigerant and may only be used in new equipment designed and listed for it under UL 60335-2-40. Arkema, which sells R-32, states there is no retrofit or drop-in replacement for R-410A, and Copeland says A2L refrigerants must not be retrofitted into non-A2L compressors or equipment.

Pressures side by side

Saturation pressure in psig at sea level. Evaporating rows use the vapor (dew) value, condensing rows the liquid (bubble) value, which is what you compare with suction and liquid-line gauges. The last column is R-32 minus R-410A.

SaturationR-410AR-32Difference
Evaporator (vapor, dew)
-20°F26.226.8+0.6 (+2%)
0°F48.249.3+1.0 (+2%)
20°F78.480.0+1.7 (+2%)
30°F97.099.1+2.1 (+2%)
35°F107.3109.7+2.3 (+2%)
40°F118.4121.0+2.6 (+2%)
45°F130.1133.0+2.9 (+2%)
50°F142.6145.9+3.2 (+2%)
Condenser (liquid, bubble)
80°F236.5241.5+4.9 (+2%)
90°F275.4281.3+6.0 (+2%)
95°F296.4302.9+6.5 (+2%)
100°F318.5325.7+7.1 (+2%)
105°F341.9349.7+7.8 (+2%)
110°F366.4374.9+8.5 (+2%)
115°F392.3401.4+9.2 (+2%)
120°F419.4429.3+9.9 (+2%)
125°F447.9458.7+10.7 (+2%)
130°F477.9489.5+11.6 (+2%)
R-410A and R-32 pressure-temperature curves compared from -40°F to 130°F
Saturation pressure of R-410A, R-32 against temperature, from the same data as the tables.

Properties

PropertyR-410AR-32
Safety classA1A2L
TypeHFC, near-azeotropic blendHFC, single-component refrigerant
Composition (mass %)R-32 50, R-125 50Single component
GWP (AR4)2,088675
LubricantPOE (PVE in some compressors)POE
Boiling point (14.7 psia)-60.6°F-61.0°F
Critical point160.4°F, 711 psia172.6°F, 839 psia
Glide at 40°F evaporating0.2°F0.0°F
Glide at 100°F condensing0.2°F0.0°F
US statusSince Jan 1 2025 no new residential or light commercial AC/HP may be made with it; servicing existing systems remains legal, and split systems built from pre-2025 components may still be installed.GWP 675 is below the 700 limit for new US residential and light commercial AC/HP from Jan 1 2025; SNAP-acceptable in new equipment subject to use conditions.

Component compatibility

ItemR-410AR-32
LubricantPOE (PVE in some compressors)POE (Copeland POE-46; Danfoss POE 185SL)
Composition50/50 blend of R-32 and R-125Single component
Equipment listingA1 equipment, no A2L listingListed for A2L under UL 60335-2-40
Recovery machineAHRI 740 machine (40 CFR 82.158 App. B3)A2L-rated machine (UL 1963 SB / 40 CFR 82.158 App. B4)
CylinderRAL 7044 gray (legacy rose)RAL 7044 gray with red band (legacy light blue-green); often left-hand thread
ChargingLiquid (near-azeotrope)No fractionation; Danfoss: initial charge as liquid
PT columnOne column is close enough (glide about 0.2°F)One column (zero glide)
New equipment (US)Only with components made or imported before Jan 1 2025Allowed (GWP 675, below 700)

What changes in the field

R-32 runs slightly above R-410A. From the PT data, R-32 is 2.6 psi higher at 40°F evaporating, and at 100°F condensing it is 325.7 psig against 318.5 psig for R-410A. Across the table the difference stays around 2%, so a gauge set to the wrong refrigerant gives a believable but wrong saturation temperature. Set the manifold to the nameplate refrigerant.

R-32 is one of the two components of R-410A, and it is a single-component fluid with zero glide. Like R-410A, it reads off one PT column. It does not fractionate, so a leak does not shift the composition of what is left in the system. Danfoss still specifies the initial charge as liquid at the condenser outlet or filter-drier. Charge fixed-orifice systems to target superheat and TXV/EEV systems to subcooling per the nameplate.

Both use POE oil. Copeland lists POE-46 for its R-32 compressors and POE-32 for R-410A, so use the oil on the compressor label, not whatever is on the truck. See refrigerant oil types.

R-32 is class A2L. Recovery machines must be certified for flammable refrigerants under 40 CFR 82.158 Appendix B4 (UL 1963 Supplement SB). New cylinders are light green-gray RAL 7044 with a red band. Many A2L cylinders use left-hand thread valves, so carry the right adapter.

Retrofit or replacement

An R-410A system cannot be converted to R-32, and the close pressures do not change that:

  1. EPA’s SNAP listing (86 FR 24444) accepts R-32 in residential and light commercial AC only in new equipment that meets use conditions based on UL 60335-2-40. Those use conditions cover charge limits and, where required, leak detection and mitigation.
  2. Copeland says A2L refrigerants must not be retrofitted into non-A2L compressors or equipment.
  3. Arkema states: “There is no retrofit or drop-in replacement for R410A.”

R-32 adapters and “conversion kits” do not make an R-410A unit an A2L-listed appliance. Repair a failed R-410A system with R-410A, or replace it with matched R-32 equipment. Repairing existing R-410A equipment remains legal. For the full rules, see R-410A phase-out and the R-410A replacement comparison.

Capacity, efficiency and cost

Arkema describes R-32 as having “higher capacity and better efficiency over R-410A,” and says its low density allows a smaller refrigerant charge. Arkema sells R-32, and it gives no figure on that page, so no percentage is quoted here. Compare the AHRI ratings of the actual matched systems.

On GWP (AR4), R-410A is 2,088 and R-32 is 675. That keeps R-32 under the 700 limit in 40 CFR 84.54 for new residential and light commercial AC and heat pumps (Jan 1 2025) and VRF (Jan 1 2026). Both are HFCs, so both fall under the AIM Act allowance phasedown: 60% of baseline in 2024–2028 and 30% in 2029–2033.

Common questions

Which cools better, R-410A or R-32?

The only performance claim in these sources is Arkema’s qualitative one in favor of R-32. Cooling output depends on the equipment, so compare rated capacity and SEER2 of the specific systems.

Can you put R-410A in an R-32 system?

No. The system is designed, tested and labeled for R-32, its compressor oil and charge are specified for R-32, and the nameplate refrigerant is the only one to use.

Is R-32 the same as R-410A?

No. R-410A is 50% R-32 and 50% R-125 by mass. R-32 alone is mildly flammable (A2L) and has a much lower GWP.

PT charts and calculators

Sources

  1. Arkema: R-32 as a replacement for R-410A forane.arkema.com
  2. Copeland AE Bulletin 93-11: Refrigerants and Lubricants Approved for Use in Copeland Compressors webapps.copeland.com
  3. Danfoss VZF compressor application guide (R-32) assets.danfoss.com
  4. 86 FR 24444 (May 6 2021), SNAP Rule 23: A2L refrigerants in residential and light commercial AC and heat pumps federalregister.gov
  5. 40 CFR 84.54: Technology Transitions restrictions ecfr.gov
  6. 40 CFR 82.158: Standards for recovery and/or recycling equipment ecfr.gov

Reviewed . Found an error? Tell us and we will correct it.