R-32 PT Chart and Refrigerant Profile

R-32 is an A2L HFC single-component refrigerant. It saturates at 121.0 psig at 40°F and 325.7 psig at 100°F.

Reviewed · PT values computed with CoolProp 8.0.0 and checked against NIST reference data (largest difference 0.1 psi)

R-32 at a glance

Safety class (ASHRAE 34)A2L: lower toxicity, mildly flammable (burning velocity ≤ 10 cm/s)
TypeHFC, single-component refrigerant
GWP (100-year, AR4)675 · AR5: 677
Ozone depletion potential0
LubricantPOE
Boiling point at 14.7 psia-61.0°F
Critical point172.6°F, 839 psia
40°F evaporating121.0 psig
100°F condensing325.7 psig
Charge asVapor or liquid
Typical useNew residential and light commercial AC and heat pumps, including ductless; Heat-pump water heaters; Scroll chillers
Trade namesForane 32 (Arkema)
US statusGWP 675 is below the 700 limit for new US residential and light commercial AC/HP from Jan 1 2025; SNAP-acceptable in new equipment subject to use conditions.
ReplacesR-410A

R-32 gauge reading to saturation temperature

psig

°F

ft

40.0°F saturation temperature at 121 psig

Enter a vacuum as a negative psig (−5 psig ≈ 10.2 in Hg). Gauges read relative to local air pressure, so above about 2,000 ft the elevation correction changes low-pressure readings noticeably. PT calculator for all refrigerants

R-32 PT chart (°F and psig)

R-32 is a single-component refrigerant, so one pressure applies at each temperature for both the evaporator and the condenser. Tap a row to load it into the lookup.

-40°F to 150°F · psig at sea level · °C and kPa in the CSV · italic = inches Hg vacuum

R-32 pressure-temperature chart, -40°F to 150°F
°Fpsig
-4011.0
-3911.7
-3812.4
-3713.0
-3613.7
-3514.4
-3415.2
-3315.9
-3216.7
-3117.4
-3018.2
-2919.0
-2819.8
-2720.6
-2621.5
-2522.3
-2423.2
-2324.1
-2225.0
-2125.9
-2026.8
-1927.8
-1828.7
-1729.7
-1630.7
-1531.7
-1432.8
-1333.8
-1234.9
-1136.0
-1037.1
-938.2
-839.4
-740.5
-641.7
-542.9
-444.2
-345.4
-246.7
-148.0
049.3
150.6
251.9
353.3
454.7
556.1
657.5
759.0
860.5
962.0
1063.5
1165.0
1266.6
1368.2
1469.8
1571.5
1673.1
1774.8
1876.5
1978.3
2080.0
2181.8
2283.6
2385.5
2487.3
2589.2
2691.1
2793.1
2895.1
2997.1
3099.1
31101.2
32103.2
33105.4
34107.5
35109.7
36111.9
37114.1
38116.4
39118.6
40121.0
41123.3
42125.7
43128.1
44130.5
45133.0
46135.5
47138.0
48140.6
49143.2
50145.9
51148.5
52151.2
53154.0
54156.7
55159.5
56162.4
57165.2
58168.1
59171.1
60174.1
61177.1
62180.1
63183.2
64186.3
65189.5
66192.7
67195.9
68199.2
69202.5
70205.8
71209.2
72212.6
73216.1
74219.6
75223.2
76226.7
77230.4
78234.0
79237.7
80241.5
81245.3
82249.1
83253.0
84256.9
85260.9
86264.9
87268.9
88273.0
89277.1
90281.3
91285.6
92289.8
93294.1
94298.5
95302.9
96307.4
97311.9
98316.4
99321.0
100325.7
101330.4
102335.1
103339.9
104344.8
105349.7
106354.6
107359.6
108364.6
109369.7
110374.9
111380.1
112385.3
113390.7
114396.0
115401.4
116406.9
117412.4
118418.0
119423.7
120429.3
121435.1
122440.9
123446.8
124452.7
125458.7
126464.7
127470.8
128477.0
129483.2
130489.5
131495.8
132502.2
133508.7
134515.2
135521.8
136528.5
137535.2
138542.0
139548.9
140555.8
141562.8
142569.8
143577.0
144584.1
145591.4
146598.7
147606.2
148613.6
149621.2
150628.8

Download the R-32 table as CSV

R-32 pressure-temperature curve from -40°F to 150°F
R-32 saturation pressure against temperature.

Where you will find R-32

R-32 (difluoromethane, HFC-32) is one of the two main refrigerants in new US residential and light commercial AC and heat pumps built since the 2025 low-GWP rule, alongside R-454B. It is common in ductless mini-splits and also used in heat-pump water heaters and scroll chillers (Arkema).

You already know the molecule. R-32 is half of R-410A by mass and more than two-thirds of R-454B. As a pure refrigerant it runs at pressures close to R-410A but slightly higher across the range.

Identify it from the nameplate and the A2L flammability markings on the unit. New cylinders are light green-gray (RAL 7044) with a red band on the shoulder or top for a flammable refrigerant. The legacy label color for R-32 is light blue-green. Equipment carries the leak detection or other mitigation that the UL 60335-2-40 based SNAP use conditions require; see refrigerant detection systems.

Charging R-32

R-32 is a single-component refrigerant, so it has no glide and does not fractionate. Vapor charging will not change its composition, a leak does not leave an off-ratio charge behind, and recovered R-32 stays R-32. Even so, follow the equipment maker’s method: the Danfoss VZF application guide calls for the initial charge in liquid phase at the condenser outlet or filter-drier (Danfoss).

With one saturation temperature per pressure, the same column serves the suction and liquid sides.

  • Fixed orifice: charge to target superheat from CEC Title 24 Table RA3.2-2 (installer tolerance ±5°F, valid at 55–115°F outdoor, return dry bulb of 70°F or more, return wet bulb of 76°F or less). Use the target superheat calculator and the superheat calculator.
  • TXV or EEV: charge by subcooling to the nameplate or manual target (Title 24 installer tolerance ±3°F) with the subcooling calculator.

Charges are small. Arkema says a typical R-32 charge is about 30% less than R-410A for the same duty (Arkema). A few ounces of error is a bigger share of the total, so weigh refrigerant in with a scale and use the manual’s line-set adder (line-set charge calculator).

Gauges and hoses must be rated for R-32 pressures. Manifolds and digital gauges need R-32 in their refrigerant list to give correct saturation temperatures.

Oil and compatibility

R-32 compressors use POE oil. Copeland lists POE-46 (with approved alternates) for its R-32 compressors (Copeland AE 93-11), and Danfoss specifies POE 185SL for its VZF line. The viscosity grade differs from typical R-410A POE-32, so add only the oil named on the compressor label or in the manual.

POE is hygroscopic. Keep the system closed, replace the filter-drier whenever you open it, and evacuate to the OEM target, typically 350–500 microns (evacuation guide). R-32 is not a retrofit for R-22 or R-410A equipment: A2L refrigerants need equipment designed and listed for them.

Safety, handling and recovery

R-32 is ASHRAE class A2L: lower toxicity, mildly flammable, burning velocity of 10 cm/s or less (flammability classes explained). Keep ignition sources out of the work area and follow the A2L service steps in the installation manual.

Use a recovery machine certified for flammable refrigerants. Under 40 CFR 82.158 that means Appendix B4, which adds UL 1963 Supplement SB to AHRI 740 (recovery machine compatibility). Many A2L cylinders use left-hand thread valves, an industry practice not specified in Guideline N-2017, so carry the right adapter.

R-32 sits just over the Section 608 pressure line. Its computed saturation pressure at 104°F is 359.4 psia (344.8 psig), above the 355 psia cutoff, so by the 40 CFR 82.152 definition R-32 equipment is very high pressure, while R-410A and R-454B are high pressure. Type II (or Universal) certification covers both classes, and Type I covers factory-sealed units of 5 lb or less. Very-high-pressure appliances must be recovered to 0 in Hg.

Status and replacements

R-32 has a GWP of 675 (AR4), below the 700 limit in the Technology Transitions rule. That makes it compliant for new residential and light commercial AC and heat pumps (from Jan 1 2025), VRF (from Jan 1 2026) and comfort chillers. EPA accepted R-32 subject to use conditions in residential and light commercial AC in SNAP Rule 23 (May 6 2021), and in chillers, residential dehumidifiers and room AC in SNAP Rule 25 (Apr 28 2023). A proposed SNAP Rule 27 (Nov 10 2025) would update use conditions but was not final as of Oct 21 2026.

R-32 is an HFC, so it counts against the AIM Act allowance phasedown: 60% of baseline in 2024–2028, 30% in 2029–2033, 20% in 2034–2035 and 15% from 2036. No successor has been set. Compare it with the other options in R-410A vs R-32, R-454B vs R-32 and the A2L refrigerants guide.

Common questions

Is R-32 flammable?

Yes, mildly. It is class A2L: it can ignite at a high enough concentration, but its burning velocity is 10 cm/s or less and its lower flammability limit is above 0.10 kg/m³, unlike class 3 refrigerants such as propane.

What oil does R-32 use?

POE. Copeland lists POE-46 and Danfoss POE 185SL for their R-32 compressors, so check the compressor label for the grade.

Can R-32 replace R-22?

Not in an existing R-22 system. R-32 needs A2L-rated equipment and runs at far higher pressure. For retrofit options see R-22 replacement refrigerants.

How this chart was computed

Every pressure on this page is calculated, not copied: CoolProp 8.0.0 (HEOS backend), the open-source implementation of the reference equations of state, using the model pure:R32. Gauge values assume sea-level air pressure (14.696 psia); kPa values in the CSV are absolute.

Spot check against NIST Chemistry WebBook, SRD 69, Thermophysical Properties of Fluid Systems: R32, saturation properties (temperature increments):

°FColumnPublishedThis chartDifference
0saturation63.9 psia64.0 psia0.0 psi
40saturation135.7 psia135.7 psia0.0 psi
120saturation444.0 psia444.0 psia0.0 psi
0saturation49.3 psig49.3 psig-0.0 psi
40saturation121.0 psig121.0 psig-0.0 psi
100saturation325.7 psig325.7 psig-0.0 psi
0saturation49.3 psig49.3 psig-0.0 psi
40saturation121.0 psig121.0 psig-0.0 psi
100saturation325.7 psig325.7 psig-0.0 psi

NIST WebBook implements the same reference equation of state as CoolProp, so near-zero deviation there confirms the implementation and unit handling; Chemours and Arkema charts agree within 0.05 psi.

Charts from different publishers can differ by a few tenths of a psi because of the equation of state and blend tolerances. Always charge to the equipment manufacturer's data. Full method and every spot check

Comparisons with R-32

Calculators for R-32

Sources

  1. Arkema Forane 32 product page forane.arkema.com
  2. Arkema: R-32 as a replacement for R-410A forane.arkema.com
  3. Danfoss VZF compressor application guide (R-32) assets.danfoss.com
  4. Copeland AE Bulletin 93-11: Refrigerants and lubricants approved for Copeland compressors webapps.copeland.com
  5. 86 FR 24444 (May 6 2021), SNAP Rule 23: A2L refrigerants in residential and light commercial AC and heat pumps federalregister.gov
  6. 88 FR 26382 (Apr 28 2023), SNAP Rule 25: A2Ls in chillers, dehumidifiers and room AC federalregister.gov
  7. 40 CFR 84.54 - Technology Transitions restrictions by sector ecfr.gov
  8. 40 CFR 82.152 - Section 608 definitions and pressure classes ecfr.gov

Reviewed . Found an error? Tell us and we will correct it.

More in Air conditioning and heat pumps