HVAC PT Data

Pressure-temperature charts, field calculators and refrigerant data for HVAC/R technicians

PT data: CoolProp 8.0 equations of state, US units

R-408A PT Chart and Refrigerant Profile

R-408A is an A1 HCFC/HFC blend near-azeotropic blend of R-125, R-143a and R-22 (7/46/47 % by mass). At 40°F its vapor (dew) pressure is 77.9 psig; at 100°F its liquid (bubble) pressure is 217.3 psig.

Reviewed · PT values computed with CoolProp 8.0.0 and checked against a published chart (largest difference 1.9 psi)

R-408A at a glance

Safety class (ASHRAE 34)A1: lower toxicity, no flame propagation
TypeHCFC/HFC blend, near-azeotropic blend
CompositionR-125 7% · R-143a 46% · R-22 47% by mass
GWP (100-year, AR4)3,152 · AR5: 3,257Counts all three components. EPA's 40 CFR 84.64 value is 2,301.2 because HCFC-22 is not counted.
Ozone depletion potential0.026
LubricantAlkylbenzene (AB), mineral oil or POE
Boiling point at 14.7 psia-47.8°F bubble · -47.0°F dew
Critical point182.3°F, 623 psia
40°F evaporating77.9 psig (dew), glide 0.6°F
100°F condensing217.3 psig (bubble), glide 0.4°F
Charge asLiquid only (blend can fractionate as vapor)
Typical useR-502 retrofit in medium- and low-temperature refrigeration (service only)
Trade namesForane FX10 (Arkema), Forane 408A (Arkema)
US statusHCFC-22 service blend; no new HCFC-22 has been produced or imported since Jan 1 2020, so supply is recovered or remaining stock.
ReplacesR-502
Replaced byR-404A

R-408A gauge reading to saturation temperature

psig

°F

ft

40.0°F vapor (dew) saturation at 78 psig: use for suction and superheat 39.5°F liquid (bubble) saturation: use for the liquid line and subcooling

Enter a vacuum as a negative psig (−5 psig ≈ 10.2 in Hg). Gauges read relative to local air pressure, so above about 2,000 ft the elevation correction changes low-pressure readings noticeably. PT calculator for all refrigerants

R-408A PT chart (°F and psig)

R-408A is a blend, so it has two saturation pressures at each temperature. Read the vapor (dew) column against suction pressure for superheat and the liquid (bubble) column against liquid-line pressure for subcooling. Tap a row to load it into the lookup.

-40°F to 150°F · psig at sea level · °C and kPa in the CSV · italic = inches Hg vacuum

R-408A pressure-temperature chart, -40°F to 150°F
°FLiquidbubble psigVapordew psig
-403.22.9
-393.73.4
-384.23.8
-374.64.3
-365.14.8
-355.65.2
-346.15.7
-336.66.2
-327.16.8
-317.77.3
-308.27.8
-298.88.4
-289.38.9
-279.99.5
-2610.510.0
-2511.110.6
-2411.711.2
-2312.311.8
-2212.912.5
-2113.513.1
-2014.213.7
-1914.814.4
-1815.515.0
-1716.215.7
-1616.916.4
-1517.617.1
-1418.317.8
-1319.018.5
-1219.819.3
-1120.520.0
-1021.320.8
-922.121.5
-822.922.3
-723.723.1
-624.523.9
-525.324.8
-426.225.6
-327.026.4
-227.927.3
-128.828.2
029.729.1
130.630.0
231.530.9
332.531.8
433.432.8
534.433.8
635.434.7
736.435.7
837.436.7
938.437.8
1039.538.8
1140.539.9
1241.640.9
1342.742.0
1443.843.1
1544.944.2
1646.145.4
1747.246.5
1848.447.7
1949.648.9
2050.850.1
2152.051.3
2253.352.5
2354.653.8
2455.855.1
2557.156.4
2658.457.7
2759.859.0
2861.160.3
2962.561.7
3063.963.1
3165.364.5
3266.765.9
3368.267.3
3469.668.8
3571.170.3
3672.671.8
3774.173.3
3875.774.8
3977.276.4
4078.877.9
4180.479.5
4282.181.2
4383.782.8
4485.484.4
4587.186.1
4688.887.8
4790.589.5
4892.291.3
4994.093.1
5095.894.8
5197.696.6
5299.598.5
53101.3100.3
54103.2102.2
55105.1104.1
56107.0106.0
57109.0108.0
58111.0109.9
59113.0111.9
60115.0113.9
61117.0116.0
62119.1118.0
63121.2120.1
64123.3122.2
65125.5124.4
66127.6126.5
67129.8128.7
68132.0130.9
69134.3133.2
70136.5135.4
71138.8137.7
72141.2140.0
73143.5142.3
74145.9144.7
75148.3147.1
76150.7149.5
77153.1152.0
78155.6154.4
79158.1156.9
80160.7159.5
81163.2162.0
82165.8164.6
83168.4167.2
84171.1169.8
85173.7172.5
86176.4175.2
87179.2177.9
88181.9180.7
89184.7183.4
90187.5186.2
91190.4189.1
92193.2191.9
93196.2194.8
94199.1197.8
95202.1200.7
96205.0203.7
97208.1206.7
98211.1209.8
99214.2212.9
100217.3216.0
101220.5219.1
102223.7222.3
103226.9225.5
104230.1228.7
105233.4232.0
106236.7235.3
107240.1238.7
108243.4242.0
109246.9245.4
110250.3248.9
111253.8252.3
112257.3255.9
113260.8259.4
114264.4263.0
115268.0266.6
116271.7270.2
117275.4273.9
118279.1277.6
119282.9281.4
120286.7285.2
121290.5289.0
122294.4292.9
123298.3296.7
124302.2300.7
125306.2304.7
126310.2308.7
127314.2312.7
128318.3316.8
129322.5320.9
130326.6325.1
131330.8329.3
132335.1333.5
133339.4337.8
134343.7342.1
135348.1346.5
136352.5350.9
137356.9355.4
138361.4359.8
139366.0364.4
140370.5368.9
141375.1373.6
142379.8378.2
143384.5382.9
144389.2387.7
145394.0392.4
146398.9397.3
147403.7402.1
148408.7407.1
149413.6412.0
150418.6417.0

Download the R-408A table as CSV

R-408A pressure-temperature curve from -40°F to 150°F, showing the bubble and dew lines
R-408A saturation pressure against temperature; the gap between the liquid and vapor lines is the glide.

Where you will find R-408A

R-408A is an HCFC service blend for R-502 equipment, sold by Arkema as Forane FX10 and Forane 408A. It combines R-22 with the HFCs R-143a and R-125. A-Gas lists it for retrofitting R-502 systems in medium- and low-temperature refrigeration, and Copeland approves it for low- and medium-temperature compressors “for service applications only”.

EPA’s SNAP program listed it on Aug 26 1994 as acceptable for retrofit in commercial ice machines, cold storage, industrial process refrigeration, remote condensing units, supermarket and stand-alone equipment, food processing and dispensing equipment, and refrigerated transport.

Look for a retrofit tag reading R-408A or FX10 on a system whose nameplate says R-502. The legacy cylinder color assigned in AHRI Guideline N-2017 was medium purple, close to R-502’s lavender; containers made since 2020 are light green-gray, so read the label.

Charging R-408A

R-408A has a small glide: 0.6°F at 40°F evaporating on this site’s table. It is still a three-part blend. Arkema’s retrofit guide says to charge it in the liquid phase only. Meter the liquid in slowly so it flashes before the compressor.

For an R-502 conversion, Arkema’s starting point is 85-90% of the original R-502 charge by weight, then adjust to the system. Arkema also says not to mix R-408A with R-502 or top off an R-502 system with it.

Arkema expects these differences against R-502:

  • Suction pressure 1-3 psi lower.
  • Discharge pressure 0-5 psi higher.
  • Discharge temperature 10-35°F higher.

This site’s tables agree on the pressures: R-408A reads 77.9 psig at a 40°F dew point against 77.5 psig for R-502, and 217.3 psig at a 100°F bubble point against 211.8 psig for R-502. Check discharge temperature against the compressor maker’s limit after a conversion.

For superheat, read suction pressure against the dew column with the superheat calculator. On TXV systems, charge by subcooling to the manufacturer’s target with the subcooling calculator, using the bubble column. With under 1°F of glide the two columns are close, but use the right one.

Oil and compatibility

R-408A can run on the oils already in an R-502 system. Arkema says no oil change is required when converting from R-502. Linde and A-Gas list mineral oil, alkylbenzene and POE.

Compressor makers are more specific:

  • Copeland prefers AB mixed with mineral oil, at least 50% AB, for retrofits. Alternates are POE-32 mixed with mineral oil (at least 50% POE) or straight POE-32.
  • BITZER lists AB, with POE “with limitations”.

Follow the compressor maker. The refrigerant oil types guide explains the oil families.

Safety, handling and recovery

R-408A is ASHRAE class A1: lower toxicity, no flame propagation. It is an ozone-depleting refrigerant, ODP 0.026 from its HCFC-22 share (40 CFR 82 Appendix B). Knowingly venting it is prohibited, recovery is required, and sales are restricted to certified technicians.

It is a high-pressure refrigerant under 40 CFR 82.152: this site’s table gives 230.1 psig (244.8 psia) at a 104°F bubble point, inside the 170-355 psia band, as for R-502 itself. Type II or Universal certification covers it.

Appliance (made on or after Nov 15 1993) Required recovery
High-pressure, under 200 lb 0 in Hg
High-pressure, 200 lb or more 10 in Hg

Appliances with 50 lb or more fall under the ODS leak-repair rules in 40 CFR 82.157. Recovered R-408A cannot be sold to a new owner unless an EPA-certified reclaimer has reclaimed it.

Status and replacements

Since Jan 1 2010, HCFC-22 may be used as a refrigerant only in equipment made before that date, and US production and import of HCFC-22 ended Jan 1 2020 (40 CFR 82.15). R-408A is therefore a service-only refrigerant on recovered, reclaimed or remaining stock. It also contains HFC-125 and HFC-143a, and the AIM Act Technology Transitions rule names it among restricted refrigerants in several new-equipment sectors, though HCFC rules already bar it from new equipment.

No source found confirms that Arkema still makes FX10; its product page no longer loads and the 2025 Technical Digest has no R-408A entry. That digest lists Forane 404A as a replacement or retrofit for R-408A.

The main paths off R-408A or R-502 are R-404A and R-507A, both on POE. The R-502 replacement comparison lines up R-408A with the HFC options, and the R-404A replacement guide covers the next step down in GWP.

Common questions

R-408A vs R-404A?

R-408A is an R-22-based service blend that can stay on the R-502 system’s oil. R-404A is an all-HFC replacement that needs POE. Arkema now lists R-404A as a retrofit for R-408A systems.

How this chart was computed

Every pressure on this page is calculated, not copied: CoolProp 8.0.0 (HEOS backend), the open-source implementation of the reference equations of state, using the model custom:R125&R143a&R22:0.07,0.46,0.47 at the nominal ASHRAE 34 composition. Gauge values assume sea-level air pressure (14.696 psia); kPa values in the CSV are absolute.

Spot check against Forane Refrigerants Pressure Temperature Chart (Arkema, 2020):

°FColumnPublishedThis chartDifference
0bubble30.1 psig29.7 psig-0.4 psi
40bubble79.7 psig78.8 psig-0.9 psi
100bubble219.2 psig217.3 psig-1.9 psi

Custom model (CoolProp cannot load R408A.mix; R-125/R-22 from the R-22/R-134a surrogate, 7 wt% R-125). Within 1.9 psi (0.8%) of Arkema (REFPROP 9.0, bubble). The NRI thermodynamic table was not used: it is 6 psi above both Arkema and NRI's own PT chart at 100 °F (NRI chart 217 psig vs table 225.6 psig).

Charts from different publishers can differ by a few tenths of a psi because of the equation of state and blend tolerances. Always charge to the equipment manufacturer's data. Full method and every spot check

Comparisons with R-408A

Calculators for R-408A

Sources

  1. ASHRAE refrigerant designations (Standard 34) ashrae.org
  2. Arkema: Retrofitting with Forane Refrigerants, Quick Reference Guide (2013) forane.arkema.com
  3. Arkema 2025 Forane Technical Digest forane.arkema.com
  4. Copeland AE Bulletin 93-11: Refrigerants and lubricants approved for Copeland compressors webapps.copeland.com
  5. BITZER Refrigerant Report (A-500/501) refrigerant data table bitzer.de
  6. A-Gas US: R408A agas.com
  7. EPA SNAP: Substitutes in typical supermarket systems epa.gov
  8. eCFR 40 CFR 82.15: Class II (HCFC) prohibitions ecfr.gov

Reviewed . Found an error? Tell us and we will correct it.