R-452B PT Chart and Refrigerant Profile

R-452B is an A2L HFC/HFO zeotropic blend of R-32, R-125 and R-1234yf (67/7/26 % by mass). At 40°F its vapor (dew) pressure is 109.4 psig; at 100°F its liquid (bubble) pressure is 306.1 psig.

Reviewed · PT values computed with CoolProp 8.0.0 and checked against a published chart (largest difference 2.5 psi)

R-452B at a glance

Safety class (ASHRAE 34)A2L: lower toxicity, mildly flammable (burning velocity ≤ 10 cm/s)
TypeHFC/HFO, zeotropic blend
CompositionR-32 67% · R-125 7% · R-1234yf 26% by mass
GWP (100-year, AR4)698 · AR5: 676698 on the usual AR4 convention; EPA's 40 CFR 84.64 calculation gives 697.5, just under the 700 limit
Ozone depletion potential0
LubricantPOE (BITZER also lists PVE)
Boiling point at 14.7 psia-59.6°F bubble · -57.8°F dew
Critical point170.9°F, 761 psia
40°F evaporating109.4 psig (dew), glide 2.2°F
100°F condensing306.1 psig (bubble), glide 2.2°F
Charge asLiquid only (blend can fractionate as vapor)
Typical useNew residential and light commercial split AC and heat pumps; Packaged and rooftop units, PTACs, mini- and multi-splits; DX chillers and VRF
Trade namesOpteon XL55 (Chemours), Solstice L41y (Honeywell; now Solstice Advanced Materials)
US statusEPA-basis GWP 697.5 is under the 700 limit for new residential and light commercial AC/HP (Jan 1 2025) and VRF (Jan 1 2026); SNAP-acceptable in new equipment only.
ReplacesR-410A

R-452B gauge reading to saturation temperature

psig

°F

ft

39.8°F vapor (dew) saturation at 109 psig: use for suction and superheat 37.6°F liquid (bubble) saturation: use for the liquid line and subcooling

Enter a vacuum as a negative psig (−5 psig ≈ 10.2 in Hg). Gauges read relative to local air pressure, so above about 2,000 ft the elevation correction changes low-pressure readings noticeably. PT calculator for all refrigerants

R-452B PT chart (°F and psig)

R-452B is a blend, so it has two saturation pressures at each temperature. Read the vapor (dew) column against suction pressure for superheat and the liquid (bubble) column against liquid-line pressure for subcooling. Tap a row to load it into the lookup.

-40°F to 150°F · psig at sea level · °C and kPa in the CSV · italic = inches Hg vacuum

R-452B pressure-temperature chart, -40°F to 150°F
°FLiquidbubble psigVapordew psig
-4010.08.9
-3910.69.5
-3811.310.1
-3711.910.7
-3612.611.4
-3513.312.0
-3413.912.7
-3314.613.3
-3215.414.0
-3116.114.7
-3016.815.4
-2917.616.2
-2818.416.9
-2719.117.7
-2619.918.4
-2520.819.2
-2421.620.0
-2322.420.8
-2223.321.7
-2124.222.5
-2025.123.3
-1926.024.2
-1826.925.1
-1727.826.0
-1628.826.9
-1529.727.9
-1430.728.8
-1331.729.8
-1232.730.8
-1133.831.8
-1034.832.8
-935.933.8
-837.034.9
-738.135.9
-639.237.0
-540.438.1
-441.539.2
-342.740.4
-243.941.5
-145.142.7
046.443.9
147.645.1
248.946.3
350.247.6
451.548.9
552.950.2
654.251.5
755.652.8
857.054.1
958.455.5
1059.956.9
1161.458.3
1262.859.8
1364.461.2
1465.962.7
1567.464.2
1669.065.7
1770.667.3
1872.268.8
1973.970.4
2075.672.0
2177.373.7
2279.075.3
2380.777.0
2482.578.7
2584.380.5
2686.182.2
2787.984.0
2889.885.8
2991.787.6
3093.689.5
3195.591.4
3297.593.3
3399.595.2
34101.597.1
35103.699.1
36105.7101.1
37107.8103.2
38109.9105.2
39112.0107.3
40114.2109.4
41116.4111.6
42118.7113.8
43121.0116.0
44123.3118.2
45125.6120.5
46128.0122.7
47130.3125.1
48132.8127.4
49135.2129.8
50137.7132.2
51140.2134.6
52142.7137.1
53145.3139.6
54147.9142.1
55150.6144.7
56153.2147.3
57155.9149.9
58158.7152.5
59161.4155.2
60164.2157.9
61167.1160.7
62169.9163.5
63172.8166.3
64175.7169.2
65178.7172.0
66181.7175.0
67184.7177.9
68187.8180.9
69190.9183.9
70194.1187.0
71197.2190.1
72200.5193.2
73203.7196.4
74207.0199.6
75210.3202.8
76213.7206.1
77217.1209.4
78220.5212.7
79224.0216.1
80227.5219.5
81231.0223.0
82234.6226.5
83238.2230.0
84241.9233.6
85245.6237.2
86249.3240.9
87253.1244.6
88257.0248.3
89260.8252.1
90264.7255.9
91268.7259.8
92272.7263.7
93276.7267.7
94280.8271.6
95284.9275.7
96289.0279.7
97293.2283.9
98297.5288.0
99301.8292.2
100306.1296.5
101310.5300.8
102314.9305.1
103319.4309.5
104323.9313.9
105328.4318.4
106333.0322.9
107337.7327.5
108342.4332.1
109347.1336.8
110351.9341.5
111356.7346.3
112361.6351.1
113366.5355.9
114371.5360.8
115376.5365.8
116381.6370.8
117386.7375.9
118391.9381.0
119397.1386.2
120402.4391.4
121407.7396.6
122413.1402.0
123418.6407.3
124424.0412.8
125429.6418.3
126435.2423.8
127440.8429.4
128446.5435.1
129452.2440.8
130458.1446.5
131463.9452.4
132469.8458.2
133475.8464.2
134481.8470.2
135487.9476.3
136494.0482.4
137500.2488.6
138506.5494.8
139512.8501.1
140519.2507.5
141525.6514.0
142532.1520.5
143538.6527.0
144545.3533.7
145551.9540.4
146558.7547.2
147565.5554.0
148572.3560.9
149579.2567.9
150586.2575.0

Download the R-452B table as CSV

R-452B pressure-temperature curve from -40°F to 150°F, showing the bubble and dew lines
R-452B saturation pressure against temperature; the gap between the liquid and vapor lines is the glide.

Where you will find R-452B

R-452B is an A2L blend for new positive-displacement air conditioning, heat pumps and chillers, in place of R-410A. Chemours sells it as Opteon XL55 and lists window units, portables, mini-splits, ducted splits, PTACs, commercial packaged units, multi-splits and DX chillers (Opteon XL55 product information). Honeywell sold it as Solstice L41y for DX chillers, high-pressure heat pumps, split AC, rooftop units and VRF.

The other A2L options in the same equipment are R-454B and R-32. Identify it by the nameplate and the A2L labels. EPA’s use conditions require red (PMS #185 or RAL 3020) hoses and piping, marked service ports and warning labels on equipment built for it.

The cylinder is the standard light green-gray (RAL 7044) with a red band on the shoulder or top for a flammable refrigerant. Guideline N-2017 Table 1 assigns R-452B no legacy color.

Charging R-452B

Charge as liquid. R-452B is a zeotropic blend of R-32, R-125 and R-1234yf, and vapor drawn off the cylinder does not match the 67/7/26 mix. We found no Chemours or Honeywell charging procedure, so the equipment installation manual is the only charging authority.

The glide is small: about 2.2°F at a 40°F dew point. At 40°F this chart gives 109.4 psig dew and 114.2 psig bubble, against 118.4 psig for R-410A. Read the right column:

  • Superheat: suction pressure against the dew column. On a fixed metering device, charge to target superheat (CEC Title 24 Table RA3.2-2, installer tolerance ±5°F, valid at 55–115°F outdoor dry bulb, return dry bulb 70°F or higher and return wet bulb 76°F or lower). Use the target superheat calculator.
  • Subcooling: liquid-line pressure against the bubble column. TXV and EEV systems are charged to the nameplate or manual subcooling target, ±3°F for the installer under Title 24. Use the subcooling calculator.

R-452B and R-454B are close but not the same, so never read one chart for the other. The temperature glide calculator shows the gap at any pressure. Line-set adders vary by manufacturer; take them from the unit’s manual.

Oil and compatibility

Equipment for R-452B ships with POE. BITZER lists POE and PVE, and the Honeywell L41y brochure recommends POE and says to check with the compressor maker. Danfoss factory-charges POE in its R-452B scrolls: 160SZ in DSH models and 215PZ or 160SZ in VZH variable-speed models, depending on size (Danfoss oil overview). Add only the oil named on the compressor, and see the refrigerant oil guide.

Chemours says Opteon XL55 is intended for new equipment design only. Do not put it in an R-410A system or top off R-410A with it.

Safety, handling and recovery

A2L means lower toxicity and mild flammability, with a burning velocity of 10 cm/s or less (flammability classes explained). EPA’s residential AC listing requires equipment that meets UL 60335-2-40, 3rd edition. Keep ignition sources away from the work area and follow the A2L service steps in the manual (A2L installation and service).

Recover with a machine certified for flammable refrigerants under 40 CFR 82.158 Appendix B4, which adds UL 1963 Supplement SB to AHRI 740 (recovery machine compatibility). Many A2L cylinders use left-hand thread valves; that is industry practice, not a Guideline N provision, so carry the adapter.

Section 608 Type II or Universal certification covers it, and Type I covers factory-sealed units of 5 lb or less. Its computed liquid saturation pressure at 104°F is 338.6 psia (323.9 psig, bubble), which makes it a high-pressure refrigerant under 40 CFR 82.152, though close to the 355 psia line. Recover appliances under 200 lb to 0 in Hg, and 200 lb or more to 10 in Hg.

Status and replacements

The GWP is the story. EPA’s 40 CFR 84.64 method gives 697.5, just under the 700 limit in 40 CFR 84.54 for new residential and light commercial AC and heat pumps (from Jan 1 2025), VRF (from Jan 1 2026), comfort chillers and data-center cooling. The common AR4 convention prints 698; AR5 gives 676. It is above the 150 and 300 limits used for refrigeration sectors.

EPA SNAP listings, all for new equipment:

  • residential and light commercial AC and heat pumps, acceptable subject to use conditions (86 FR 24444, May 6 2021)
  • centrifugal and positive-displacement comfort chillers, industrial process AC and residential dehumidifiers (88 FR 26382, Apr 28 2023)

R-452B is not on EPA’s pages for retail food, cold storage, transport or ice rinks. Its R-32 and R-125 count against the AIM Act phasedown (60% of baseline in 2024–2028, 30% in 2029–2033); R-1234yf is not a regulated substance under Part 84.

No source names a successor. For how it fits next to the other R-410A alternatives, see R-410A replacement options, R-410A vs R-454B and the A2L refrigerants guide.

Common questions

Is Opteon XL55 the same as R-452B?

Yes. Opteon XL55 is Chemours’ name for R-452B, and Solstice L41y is the Honeywell name for the same blend.

Can R-452B replace R-410A in an existing system?

No. EPA lists it for new equipment only, Chemours says XL55 is for new equipment design, and the system needs A2L-rated components and mitigation. See R-410A replacement options.

How this chart was computed

Every pressure on this page is calculated, not copied: CoolProp 8.0.0 (HEOS backend), the open-source implementation of the reference equations of state, using the model mix:R452B at the nominal ASHRAE 34 composition. Gauge values assume sea-level air pressure (14.696 psia); kPa values in the CSV are absolute.

Spot check against Honeywell Solstice L41y (R-452B) brochure, FPR-031-2018-01-EN (2018), "Pressure and temperature" table:

°FColumnPublishedThis chartDifference
-33.0bubble200.0 kPa202.0 kPa+0.3 psi
-31.4dew200.0 kPa201.1 kPa+0.2 psi
34.4bubble800.0 kPa806.8 kPa+1.0 psi
36.4dew800.0 kPa804.4 kPa+0.6 psi
112.7bubble2,600.0 kPa2,617.5 kPa+2.5 psi
114.6dew2,600.0 kPa2,610.3 kPa+1.5 psi

Honeywell table is pressure-based (bar abs in, °C out to 0.01 °C); computed pressure at the printed temperature. Within 1 psi up to 36 °F; 2.5 psi (0.6%) high on the bubble side at 113 °F. Chemours XL55 PT data could not be retrieved; the Honeywell brochure is cited from its Wayback Machine copy.

Charts from different publishers can differ by a few tenths of a psi because of the equation of state and blend tolerances. Always charge to the equipment manufacturer's data. Full method and every spot check

Calculators for R-452B

Sources

  1. Chemours: Opteon XL55 (R-452B) product information (C-10214, 5/16) opteon.com
  2. Honeywell Solstice L41y (R-452B) brochure (Wayback copy) web.archive.org
  3. EPA SNAP: Substitutes in residential and light commercial AC and heat pumps epa.gov
  4. 86 FR 24444 (May 6 2021): SNAP Rule 23, A2L refrigerants in residential and light commercial AC govinfo.gov
  5. 88 FR 26382 (Apr 28 2023): SNAP listings for chillers, industrial process AC and dehumidifiers govinfo.gov
  6. 40 CFR 84.64: GWPs for Technology Transitions ecfr.gov
  7. 40 CFR 84.54: Technology Transitions restrictions by sector ecfr.gov
  8. Danfoss Commercial Compressors: overview of oil types (2025.03) assets.danfoss.com

Reviewed . Found an error? Tell us and we will correct it.