R-434A (RS-45) PT Chart and Refrigerant Profile

R-434A (RS-45) is an A1 HFC/HC zeotropic blend of R-125, R-143a, R-134a and R-600a (63.2/18/16/2.8 % by mass). At 40°F its vapor (dew) pressure is 77.3 psig; at 100°F its liquid (bubble) pressure is 228.4 psig.

Reviewed · PT values computed with CoolProp 8.0.0 and checked against a published chart (largest difference 7.8 psi)

Accuracy note. The open mixture model used for R-434A gives vapor (dew) pressures up to 7.8 psi above the manufacturer's published chart (at 100.4°F). The difference is listed in How this chart was computed. When you set a charge on R-434A, use the manufacturer's chart or the equipment charging chart.

R-434A at a glance

Safety class (ASHRAE 34)A1: lower toxicity, no flame propagation
TypeHFC/HC, zeotropic blend
CompositionR-125 63.2% · R-143a 18% · R-134a 16% · R-600a 2.8% by mass
GWP (100-year, AR4)3,245 · AR5: 3,075EPA's 40 CFR 84.64 calculation gives 3,245.4.
Ozone depletion potential0
LubricantMineral oil, AB or POE (BITZER lists POE only)
Boiling point at 14.7 psia-49.4°F bubble · -44.2°F dew
Critical point165.1°F, 541 psia
40°F evaporating77.3 psig (dew), glide 3.6°F
100°F condensing228.4 psig (bubble), glide 2.5°F
Charge asLiquid only (blend can fractionate as vapor)
Typical useR-22 retrofit in commercial AC and water chillers, including flooded evaporators; Low-, medium- and high-temperature commercial refrigeration; Transport refrigeration, dairy and cellar cooling
Trade namesRS-45 (Refrigerant Solutions Ltd; A-Gas; ComStar in the US)
US statusRetrofit and service refrigerant only; its GWP of about 3,245 is above every 40 CFR 84.54 limit for new equipment, and it is named for new refrigerated transport (2025).
ReplacesR-22

R-434A gauge reading to saturation temperature

psig

°F

ft

39.8°F vapor (dew) saturation at 77 psig: use for suction and superheat 36.2°F liquid (bubble) saturation: use for the liquid line and subcooling

Enter a vacuum as a negative psig (−5 psig ≈ 10.2 in Hg). Gauges read relative to local air pressure, so above about 2,000 ft the elevation correction changes low-pressure readings noticeably. PT calculator for all refrigerants

R-434A PT chart (°F and psig)

R-434A is a blend, so it has two saturation pressures at each temperature. Read the vapor (dew) column against suction pressure for superheat and the liquid (bubble) column against liquid-line pressure for subcooling. Tap a row to load it into the lookup.

-40°F to 150°F · psig at sea level · °C and kPa in the CSV · italic = inches Hg vacuum

R-434A pressure-temperature chart, -40°F to 150°F
°FLiquidbubble psigVapordew psig
-404.01.7
-394.52.2
-385.02.6
-375.53.1
-366.03.5
-356.54.0
-347.04.5
-337.65.0
-328.15.5
-318.76.0
-309.26.6
-299.87.1
-2810.47.6
-2711.08.2
-2611.68.8
-2512.29.3
-2412.89.9
-2313.510.5
-2214.111.1
-2114.811.8
-2015.512.4
-1916.213.0
-1816.913.7
-1717.614.4
-1618.315.1
-1519.015.8
-1419.816.5
-1320.617.2
-1221.317.9
-1122.118.7
-1022.919.4
-923.720.2
-824.621.0
-725.421.8
-626.322.6
-527.123.4
-428.024.2
-328.925.1
-229.826.0
-130.826.9
031.727.7
132.728.7
233.629.6
334.630.5
435.631.5
536.632.5
637.733.4
738.734.4
839.835.5
940.936.5
1042.037.5
1143.138.6
1244.239.7
1345.340.8
1446.541.9
1547.743.0
1648.944.2
1750.145.4
1851.346.5
1952.647.7
2053.849.0
2155.150.2
2256.451.5
2357.852.7
2459.154.0
2560.555.3
2661.856.7
2763.258.0
2864.659.4
2966.160.8
3067.562.2
3169.063.6
3270.565.0
3372.066.5
3473.568.0
3575.169.5
3676.771.0
3778.372.6
3879.974.1
3981.575.7
4083.277.3
4184.979.0
4286.680.6
4388.382.3
4490.084.0
4591.885.7
4693.687.5
4795.489.2
4897.291.0
4999.192.8
50101.094.7
51102.996.5
52104.898.4
53106.7100.3
54108.7102.2
55110.7104.2
56112.7106.1
57114.8108.1
58116.8110.2
59118.9112.2
60121.0114.3
61123.2116.4
62125.3118.5
63127.5120.7
64129.8122.8
65132.0125.0
66134.3127.3
67136.6129.5
68138.9131.8
69141.2134.1
70143.6136.5
71146.0138.8
72148.5141.2
73150.9143.6
74153.4146.1
75155.9148.5
76158.4151.0
77161.0153.6
78163.6156.1
79166.2158.7
80168.9161.3
81171.6164.0
82174.3166.7
83177.0169.4
84179.8172.1
85182.6174.9
86185.4177.7
87188.3180.5
88191.2183.4
89194.1186.3
90197.1189.2
91200.1192.1
92203.1195.1
93206.1198.1
94209.2201.2
95212.3204.3
96215.4207.4
97218.6210.5
98221.8213.7
99225.1216.9
100228.4220.2
101231.7223.5
102235.0226.8
103238.4230.2
104241.8233.6
105245.2237.0
106248.7240.4
107252.2243.9
108255.8247.5
109259.4251.0
110263.0254.7
111266.6258.3
112270.3262.0
113274.1265.7
114277.8269.5
115281.6273.3
116285.5277.1
117289.4281.0
118293.3284.9
119297.2288.8
120301.2292.8
121305.2296.9
122309.3301.0
123313.4305.1
124317.6309.2
125321.8313.4
126326.0317.7
127330.3322.0
128334.6326.3
129338.9330.7
130343.3335.1
131347.8339.6
132352.3344.1
133356.8348.6
134361.4353.2
135366.0357.9
136370.6362.6
137375.3367.3
138380.1372.1
139384.9376.9
140389.7381.8
141394.6386.8
142399.5391.8
143404.5396.8
144409.5401.9
145414.6407.0
146419.7412.3
147424.9417.5
148430.1422.8
149435.4428.2
150440.7433.6

Download the R-434A table as CSV

R-434A pressure-temperature curve from -40°F to 150°F, showing the bubble and dew lines
R-434A saturation pressure against temperature; the gap between the liquid and vapor lines is the glide.

Where you will find R-434A

R-434A is RS-45, an R-22 retrofit blend from Refrigerant Solutions Ltd that A-Gas sells in Canada and South Africa and Gas Servei sells in Spain. In the US, a 2026 ChemPoint page lists ComStar RS-45 as a current product, described as a drop-in replacement for R-22 with no oil, system or component change required.

A-Gas Canada lists commercial AC, transport refrigeration, food retail, dairy chillers, cellar cooling and water chillers. It calls RS-45 the only R-22 replacement suitable for flooded evaporators; that is the supplier’s claim, not an independent test. Gas Servei positions it for large AC and general refrigeration with TXVs, evaporating down to -35°C (-31°F).

Look for it in converted R-22 chillers, condensing units and refrigeration systems. The nameplate keeps the R-22 rating, so the retrofit label is the identifier. The legacy label color is sulfur yellow (PMS 388) under AHRI Guideline N-2017.

Unlike most R-22 drop-ins, it contains R-143a, one of the two main components of R-404A. Its pressures run above R-22.

Charging R-434A

Accuracy note: this site’s computed R-434A chart reads 1.2 to 7.8 psi (about 2.6–3.3%) above the only published reference we found, the RSL RS-45 table, with the largest gaps at condensing temperatures. When you set a charge, use the RSL or supplier chart or the equipment charging chart, not the computed values on this page.

Always charge liquid. A-Gas South Africa says it must be charged from the liquid phase, and Gas Servei says to always load it as liquid. It is a zeotrope with a few degrees of glide, so read the dew column for superheat and the bubble column for subcooling, using the supplier’s chart.

On fixed metering devices, set the charge by target superheat. On TXV and EEV systems, use the manufacturer’s subcooling target. Gas Servei notes the expansion valve may need to be opened or adjusted after conversion. We found no RS-45 charge-weight guidance, so follow the equipment manufacturer and add liquid in small steps toward the system’s targets.

Gas Servei says a system can be refilled after a leak. Repair the leak first.

Oil and compatibility

Suppliers differ on oil:

  • A-Gas Canada: works with mineral oil, AB and POE; no oil change is needed going from R-22, but follow the compressor maker.
  • A-Gas South Africa: works with most current oils, POE preferred.
  • Gas Servei: compatible with the original system oil.
  • BITZER: POE only.

If the compressor is a BITZER, or the manufacturer’s approval list calls for POE, change the oil. Replace the filter-drier when the system is open and evacuate to the OEM target (evacuation guide). More in the refrigerant oil guide.

Safety, handling and recovery

R-434A is A1 (lower toxicity, no flame propagation) per BITZER, A-Gas and EPA, despite the 2.8% isobutane.

It is a Section 608 high-pressure refrigerant. Its liquid saturation pressure at 104°F sits well inside the 170–355 psia band, even allowing for the chart difference above. Type II or Universal certification covers it, and sales have been limited to certified technicians since Jan 1 2018. Recover appliances made after Nov 15 1993 to 0 in Hg under 200 lb of charge and 10 in Hg at 200 lb or more (refrigerant recovery).

New cylinders since Jan 1 2020 are light green-gray (RAL 7044); sulfur yellow appears on the label only (cylinder colors).

Status and replacements

EPA SNAP has listed R-434A as acceptable, retrofit and new, since Oct 4 2007 in residential and light commercial AC, industrial process AC and refrigeration, refrigerated transport, water coolers, ice machines, ice rinks and dehumidifiers. The supermarket systems and remote condensing unit pages show it as unacceptable for retrofit from July 20 2016. Court decisions (Mexichem Fluor v. EPA, 2017 and 2019) partly vacated those 2015 listings, but EPA’s pages still print them, so check the current rule before converting a rack.

Its AR4 GWP of about 3,245 is above every Technology Transitions limit for new equipment. 40 CFR 84.54 also names it for new road and marine refrigerated transport (Jan 1 2025), several ice machine and food processing categories (Jan 1 2027) and UL 621 ice cream makers (Jan 1 2028). Servicing existing systems remains legal, and the leak repair rule applies to appliances with 15 lb or more of HFC from Jan 1 2026.

No source names a successor. Compare lower-GWP routes off R-22 in R-22 replacement options, and see the GWP chart for how it ranks.

Common questions

What is R-434A used for?

It is an R-22 retrofit for existing AC, chillers and refrigeration. A-Gas lists low-, medium- and high-temperature uses, including flooded evaporators.

What is the GWP of R-434A?

About 3,245 on the AR4 basis that EPA uses (3,245.4 by EPA’s 40 CFR 84.64 method), against an AR4 value of 1,810 for R-22.

How this chart was computed

Every pressure on this page is calculated, not copied: CoolProp 8.0.0 (HEOS backend), the open-source implementation of the reference equations of state, using the model mix:R434A at the nominal ASHRAE 34 composition. Gauge values assume sea-level air pressure (14.696 psia); kPa values in the CSV are absolute.

Spot check against RS-45 (R434A) Pressure & Temperature Table: Absolute, Refrigerant Solutions Ltd (undated):

°FColumnPublishedThis chartDifference
-0.4bubble44.8 psia46.0 psia+1.2 psi
-0.4dew40.9 psia42.1 psia+1.2 psi
39.2bubble94.1 psia96.5 psia+2.4 psi
39.2dew87.9 psia90.8 psia+2.8 psi
100.4bubble238.1 psia244.4 psia+6.3 psi
100.4dew228.4 psia236.2 psia+7.8 psi

mix:R434A (all pairs fitted) reads 1.2-7.8 psi (2.6-3.3%) above the only reference found, the RSL RS-45 table (compared at -18, 4, 38 °C). Low-temperature agreement is better (normal boiling point -49.4 °F vs RSL -48.8 °F bubble). No second source found. Kept with disclosure.

Charts from different publishers can differ by a few tenths of a psi because of the equation of state and blend tolerances. Always charge to the equipment manufacturer's data. Full method and every spot check

Calculators for R-434A

Sources

  1. A-Gas Canada: RS-45 (R434A) agas.com
  2. A-Gas South Africa: R434A (RS-45) agas.com
  3. Gas Servei: RS-45 (R-434A) gas-servei.com
  4. ChemPoint: ComStar Refrigerants (2026) chempoint.com
  5. Refrigerant Solutions Ltd: RS-45 (R434A) pressure and temperature table refsols.com
  6. BITZER Refrigerant Report: refrigerant data table bitzer.de
  7. EPA SNAP: Substitutes in supermarket systems epa.gov
  8. 40 CFR 84.54: Technology Transitions restrictions by sector ecfr.gov

Reviewed . Found an error? Tell us and we will correct it.