Refrigerant GWP chart

GWP compares how much heat a gas traps over 100 years against the same mass of CO2. US rules use the IPCC AR4 values in 40 CFR 84 Appendix A, so R-410A is 2,088 and R-454B is 466 (EPA's own calculation gives 465). Blend GWP is the mass-weighted sum of its components.

Reviewed against the sources listed at the end of this page

Key facts

  • EPA exchange values are IPCC AR4 100-year GWPs (40 CFR 84 Appendix A): R-32 675, R-125 3,500, R-134a 1,430, R-143a 4,470.
  • Blend GWP = sum of (mass fraction × component GWP) under 40 CFR 84.64; R-410A = 50% × 675 + 50% × 3,500 = 2,087.5.
  • 40 CFR 84.64 assigns HFO-1234yf and HFO-1234ze(E) a GWP of 1, R-290 3.3 and R-600a 1; many published blend figures use 4 for R-1234yf.
  • New residential and light commercial AC and heat pumps: GWP limit 700 from Jan 1 2025 (40 CFR 84.54).
  • AR5 and AR6 give different numbers for the same refrigerant. They are basis differences, not errors.

What GWP means

Global warming potential (GWP) is the heat a gas traps over a set period compared with the same mass of carbon dioxide, which is 1 by definition. Refrigerant charts and US rules use the 100-year value. A GWP of 2,088 means one pound released traps as much heat over 100 years as 2,088 pounds of CO2.

GWP says nothing about ozone depletion, flammability or efficiency. R-22 has a lower GWP than R-410A but depletes ozone, which is why it was phased out under a different program (40 CFR 82). R-32 has a lower GWP than R-410A but is flammable (A2L).

AR4, AR5, AR6: why sites print different numbers

The IPCC has published GWP tables in several assessment reports, and each revision changes the values:

Refrigerant AR4 AR5 AR6
R-32 675 677 771
R-125 3,500 3,170 3,740
R-134a 1,430 1,300 1,530
R-410A (50/50 R-32/R-125) 2,088 1,924 2,256

US regulation uses AR4. The exchange values in 40 CFR 84 Appendix A are the AR4 100-year GWPs: HFC-32 675, HFC-125 3,500, HFC-134a 1,430, HFC-143a 4,470, HFC-152a 124, HFC-23 14,800, HFC-227ea 3,220. Those are the numbers behind the AIM Act phasedown and the Technology Transitions limits.

For R-454B you will see 466 (AR4 with R-1234yf at 4, the common published value), 465 (EPA’s 40 CFR 84.64 calculation), 467 (AR5), 470 (EPA’s SNAP page, rounded) and 531 (AR6). All are correct for their basis. When two sources disagree, check the basis before assuming one is wrong. This site states AR4 everywhere and gives EPA’s value in a note where it differs.

How blend GWP is calculated

40 CFR 84.64 defines the method: the blend GWP is the sum of each constituent’s GWP multiplied by its nominal mass fraction.

  • R-410A (50% R-32, 50% R-125): 0.50 × 675 + 0.50 × 3,500 = 2,087.5, published as 2,088.
  • R-407C (23% R-32, 25% R-125, 52% R-134a): 0.23 × 675 + 0.25 × 3,500 + 0.52 × 1,430 = 1,773.9, published as 1,774.
  • R-454B (68.9% R-32, 31.1% R-1234yf): with R-1234yf at 4, 465.1 + 1.2 = 466.3. With EPA’s value of 1, the result is 465.4.

The difference comes from the non-HFC constituents. AR4 has no value for HFOs or hydrocarbons, so 84.64 Table 1 assigns them: HFO-1234yf 1, HFO-1234ze(E) 1, HCFO-1233zd(E) 4, R-290 3.3, R-600 4, R-600a 1, R-717 1, R-744 1. Constituents with no listed value, such as HCFCs, CFCs and PFC-116, are left out of the sum (84.64(c)). That is why EPA’s figure for R-508B counts only its HFC-23 share and why R-401A comes out near 16 under 84.64.

The limits that use these numbers

The Technology Transitions rule (40 CFR 84.54) restricts new systems by GWP, sector by sector. For equipment a field tech meets most:

Sector (new systems) GWP limit Effective
Residential and light commercial AC and heat pumps (not VRF) 700 Jan 1 2025
VRF residential and light commercial AC/HP 700 Jan 1 2026
Comfort cooling chillers 700 Jan 1 2025
Data center and computer room cooling 700 Jan 1 2027
Cold storage warehouses 700, then 150 or 300 July 27 2026; Jan 1 2032
Retail food remote condensing units 1,400, then 150 or 300 July 27 2026; Jan 1 2032
Supermarket systems 1,400, then 150 or 300 Jan 1 2027; Jan 1 2032

From 2032 the cold storage, remote condensing unit and supermarket limits are 150 for systems of 200 lb or more charge (other than the high side of a cascade), and 300 for systems under 200 lb and for the high side of cascades.

The May 2026 final rule (91 FR 31284, effective July 27 2026) lets new residential and light commercial split systems with GWP of 700 or more still be installed where all specified components were manufactured or imported before Jan 1 2025, with no end date. Servicing and repairing existing R-410A equipment remains legal. See the R-410A phase-out and the AIM Act rules for the full picture.

Two numbers sit close to the lines. R-32 (675) and R-513A (631) are under 700. R-449A (1,396.3 under 84.64) and R-448A (1,386.1) are under 1,400. EPA’s SNAP page rounds R-449A to 1,400, so use the 84.64 value when a limit is at stake.

Separately, the AIM Act phasedown caps HFC production and import on an exchange-value-weighted basis (40 CFR 84.7): 90% of baseline in 2022–2023, 60% in 2024–2028, 30% in 2029–2033, 20% in 2034–2035 and 15% from 2036. HFOs are not regulated substances under Part 84.

GWP chart: 62 refrigerants

Sorted from highest to lowest GWP. “GWP, AR4 basis” is the IPCC AR4 100-year value (mass-weighted for blends, with HFO constituents at the common industry values of 4 for R-1234yf and 6 for R-1234ze(E)). “EPA 40 CFR 84.64 value” is the figure EPA computes for Technology Transitions limits; a dash means the refrigerant has no Part 84 value. Safety classes are ASHRAE Standard 34.

Refrigerant Type Safety class GWP, AR4 basis EPA 40 CFR 84.64 value Note
R-23 HFC A1 14,800 14,800
R-508B HFC/PFC A1 13,396 6,808 84.64 counts only the HFC-23 share (PFC-116 has no value)
R-12 CFC A1 10,900 — CFC, ozone-depleting; no Part 84 value
R-500 CFC/HFC azeotrope A1 8,077 32.5 84.64 counts only the HFC-152a share
R-14 (tetrafluoromethane) PFC A1 7,390 — Perfluorocarbon; not an AIM Act regulated substance
R-113 CFC A1 6,130 — CFC, ozone-depleting; no Part 84 value
R-11 CFC A1 4,750 — CFC, ozone-depleting; no Part 84 value
R-502 CFC A1 4,657 — CFC/HCFC blend; no Part 84 value
R-143a HFC A2L 4,470 4,470 Blend component
R-507A HFC A1 3,985 3,985
R-404A HFC A1 3,922 3,921.6
R-125 HFC A1 3,500 3,500 Blend component
R-434A (RS-45) HFC/HC A1 3,245 3,245.4
R-408A HCFC/HFC blend A1 3,152 2,301.2 84.64 does not count HCFC-22
R-422A (MO79) HFC/HC A1 3,143 3,143
R-422D (MO29) HFC/HC A1 2,729 2,729 R-600a counted at the 84.64 value
R-421A HFC A1 2,631 2,630.6
R-422B (NU-22B) HFC/HC A1 2,526 2,525.6 R-600a counted at the 84.64 value
R-424A (RS-44) HFC/HC A1 2,440 2,439.6 Isopentane excluded
R-417A HFC/HC A1 2,346 2,346.1 R-600 counted at the 84.64 value
R-438A (MO99) HFC/HC A1 2,265 2,264.5 R-600 counted at the 84.64 value; R-601a excluded
R-452A HFC/HFO A1 2,140 2,139.6 HFO counted at the industry value
R-427A HFC A1 2,138 2,138.3
R-407A HFC A1 2,107 2,107
R-410A HFC A1 2,088 2,087.5
R-407F HFC A1 1,825 1,824.5
R-22 HCFC A1 1,810 — HCFC, ozone-depleting; no Part 84 value
R-437A HFC/HC blend A1 1,805 1,805.1 Butane counted at the industry value; pentane excluded
R-407C HFC A1 1,774 1,773.9
R-453A (RS-70) HFC/HC A1 1,765 1,765.4 R-600 counted at the 84.64 value; R-601a excluded
R-458A (TdX 20) HFC A1 1,650 1,650
R-409A HCFC blend A1 1,585 — HCFC blend; no Part 84 value
R-407H HFC A1 1,495 1,495.1
R-134a HFC A1 1,430 1,430
R-449A HFC/HFO A1 1,397 1,396.3 HFO counted at the industry value
R-448A HFC/HFO A1 1,387 1,386.1 HFO counted at the industry value
R-401B HCFC blend A1 1,288 13.6 84.64 counts only the HFC-152a share
R-401A HCFC blend A1 1,182 16.1 84.64 counts only the HFC-152a share
R-416A HCFC/HFC blend A1 1,084 843.8 84.64 does not count HCFC-124
R-245fa HFC B1 1,030 1,030
R-452B HFC/HFO A2L 698 697.5 Just under the 700 limit on the EPA basis
R-32 HFC A2L 675 675
R-513A HFC/HFO A1 631 629.8 HFO counted at the industry value
R-450A HFC/HFO blend A1 604 601.2 HFO counted at the industry value
R-454B HFC/HFO A2L 466 465.4 Commonly published as 466; EPA calculation gives 465
R-515B HFC/HFO A1 292 287.5 HFO counted at the industry value
R-454A HFC/HFO A2L 239 236.9 HFO counted at the industry value
R-454C HFC/HFO A2L 148 145.9 HFO counted at the industry value
R-455A HFC/HFO A2L 148 145.9 HFO counted at the industry value
R-152a HFC A2 124 124
R-123 HCFC B1 77 — HCFC; no Part 84 value
R-170 (ethane) HC A3 Not in AR4 5.5 Hydrocarbon; 84.64 value
R-1233zd(E) HCFO A1 Not in AR4 4 EPA SNAP chiller page lists 4.7-7
R-290 (propane) HC A3 Not in AR4 3.3 Hydrocarbon; EPA SNAP pages list 3
R-1336mzz(Z) HFO A1 Not in AR4 2 HFO; EPA SNAP chiller page lists 9
R-1270 (propylene) HC A3 Not in AR4 1.8 Hydrocarbon; EPA SNAP pages list 1.8 or 5
R-1234yf HFO A2L Not in AR4 1 HFO; EPA MVAC page lists 4; AR5 less than 1
R-1234ze(E) HFO A2L Not in AR4 1 HFO; EPA SNAP chiller page lists 6; AR5 less than 1
R-600a (isobutane) HC A3 Not in AR4 1 Hydrocarbon; EPA SNAP pages list 3
R-717 (ammonia) Natural B2L Not in AR4 1 No IPCC value; EPA SNAP pages list 0
R-744 (CO2) Natural A1 1 1 Reference gas, 1 by definition
R-514A HFO/HCO B1 Not in AR4 — Not an AIM Act regulated substance; EPA SNAP chiller page lists 7

Reading the chart

  • Ozone-depleting refrigerants (R-11, R-12, R-113, R-22, R-123, R-502, R-500, R-401A, R-401B, R-408A, R-409A, R-416A) carry AR4 GWPs, but only their HFC share, if any, has a Part 84 value. They are controlled under 40 CFR 82, not the AIM Act.
  • HFO, HCFO and natural refrigerants have no AR4 listing. Their EPA values come from 84.64 Table 1, and EPA’s program pages sometimes print different figures (for example 4 for R-1234yf on the MVAC page, 3 for propane on SNAP pages).
  • Safety class matters as much as GWP. The R-410A replacements in new residential and light commercial AC, R-32 and R-454B, are both A2L. See A2L refrigerants for what changes in handling.
  • GWP is not a retrofit guide. A lower-GWP refrigerant still has to suit the equipment, oil and safety listing. See the R-410A replacement and R-22 replacement pages, and refrigerant oil types for lubricant changes.

Related

Sources

  1. 40 CFR Part 84 Appendix A: Regulated substances and exchange values ecfr.gov
  2. 40 CFR 84.64: Global warming potentials (blend calculation and constituent values) ecfr.gov
  3. 40 CFR 84.54: Technology Transitions restrictions by sector ecfr.gov
  4. 40 CFR 84.7: HFC production and consumption phasedown schedule ecfr.gov
  5. 91 FR 31284 (May 26 2026): Reconsideration of Certain Technology Transitions Requirements, final rule federalregister.gov
  6. IPCC AR4 WG1 Chapter 2, Table 2.14 (100-year GWP) ipcc.ch
  7. IPCC AR5 WG1 Chapter 8, Appendix 8.A, Table 8.A.1 ipcc.ch
  8. IPCC AR6 WG1 Chapter 7 Supplementary Material, Table 7.SM.7 ipcc.ch
  9. EPA: MVAC acceptable refrigerants and their impacts epa.gov
  10. UNEP/ASHRAE Factsheet: Refrigerant designations and safety classifications (ASHRAE 34-2024) ashrae.org