Refrigerant GWP chart
GWP compares how much heat a gas traps over 100 years against the same mass of CO2. US rules use the IPCC AR4 values in 40 CFR 84 Appendix A, so R-410A is 2,088 and R-454B is 466 (EPA's own calculation gives 465). Blend GWP is the mass-weighted sum of its components.
Reviewed against the sources listed at the end of this page
Key facts
- EPA exchange values are IPCC AR4 100-year GWPs (40 CFR 84 Appendix A): R-32 675, R-125 3,500, R-134a 1,430, R-143a 4,470.
- Blend GWP = sum of (mass fraction × component GWP) under 40 CFR 84.64; R-410A = 50% × 675 + 50% × 3,500 = 2,087.5.
- 40 CFR 84.64 assigns HFO-1234yf and HFO-1234ze(E) a GWP of 1, R-290 3.3 and R-600a 1; many published blend figures use 4 for R-1234yf.
- New residential and light commercial AC and heat pumps: GWP limit 700 from Jan 1 2025 (40 CFR 84.54).
- AR5 and AR6 give different numbers for the same refrigerant. They are basis differences, not errors.
What GWP means
Global warming potential (GWP) is the heat a gas traps over a set period compared with the same mass of carbon dioxide, which is 1 by definition. Refrigerant charts and US rules use the 100-year value. A GWP of 2,088 means one pound released traps as much heat over 100 years as 2,088 pounds of CO2.
GWP says nothing about ozone depletion, flammability or efficiency. R-22 has a lower GWP than R-410A but depletes ozone, which is why it was phased out under a different program (40 CFR 82). R-32 has a lower GWP than R-410A but is flammable (A2L).
AR4, AR5, AR6: why sites print different numbers
The IPCC has published GWP tables in several assessment reports, and each revision changes the values:
| Refrigerant | AR4 | AR5 | AR6 |
|---|---|---|---|
| R-32 | 675 | 677 | 771 |
| R-125 | 3,500 | 3,170 | 3,740 |
| R-134a | 1,430 | 1,300 | 1,530 |
| R-410A (50/50 R-32/R-125) | 2,088 | 1,924 | 2,256 |
US regulation uses AR4. The exchange values in 40 CFR 84 Appendix A are the AR4 100-year GWPs: HFC-32 675, HFC-125 3,500, HFC-134a 1,430, HFC-143a 4,470, HFC-152a 124, HFC-23 14,800, HFC-227ea 3,220. Those are the numbers behind the AIM Act phasedown and the Technology Transitions limits.
For R-454B you will see 466 (AR4 with R-1234yf at 4, the common published value), 465 (EPA’s 40 CFR 84.64 calculation), 467 (AR5), 470 (EPA’s SNAP page, rounded) and 531 (AR6). All are correct for their basis. When two sources disagree, check the basis before assuming one is wrong. This site states AR4 everywhere and gives EPA’s value in a note where it differs.
How blend GWP is calculated
40 CFR 84.64 defines the method: the blend GWP is the sum of each constituent’s GWP multiplied by its nominal mass fraction.
- R-410A (50% R-32, 50% R-125): 0.50 × 675 + 0.50 × 3,500 = 2,087.5, published as 2,088.
- R-407C (23% R-32, 25% R-125, 52% R-134a): 0.23 × 675 + 0.25 × 3,500 + 0.52 × 1,430 = 1,773.9, published as 1,774.
- R-454B (68.9% R-32, 31.1% R-1234yf): with R-1234yf at 4, 465.1 + 1.2 = 466.3. With EPA’s value of 1, the result is 465.4.
The difference comes from the non-HFC constituents. AR4 has no value for HFOs or hydrocarbons, so 84.64 Table 1 assigns them: HFO-1234yf 1, HFO-1234ze(E) 1, HCFO-1233zd(E) 4, R-290 3.3, R-600 4, R-600a 1, R-717 1, R-744 1. Constituents with no listed value, such as HCFCs, CFCs and PFC-116, are left out of the sum (84.64(c)). That is why EPA’s figure for R-508B counts only its HFC-23 share and why R-401A comes out near 16 under 84.64.
The limits that use these numbers
The Technology Transitions rule (40 CFR 84.54) restricts new systems by GWP, sector by sector. For equipment a field tech meets most:
| Sector (new systems) | GWP limit | Effective |
|---|---|---|
| Residential and light commercial AC and heat pumps (not VRF) | 700 | Jan 1 2025 |
| VRF residential and light commercial AC/HP | 700 | Jan 1 2026 |
| Comfort cooling chillers | 700 | Jan 1 2025 |
| Data center and computer room cooling | 700 | Jan 1 2027 |
| Cold storage warehouses | 700, then 150 or 300 | July 27 2026; Jan 1 2032 |
| Retail food remote condensing units | 1,400, then 150 or 300 | July 27 2026; Jan 1 2032 |
| Supermarket systems | 1,400, then 150 or 300 | Jan 1 2027; Jan 1 2032 |
From 2032 the cold storage, remote condensing unit and supermarket limits are 150 for systems of 200 lb or more charge (other than the high side of a cascade), and 300 for systems under 200 lb and for the high side of cascades.
The May 2026 final rule (91 FR 31284, effective July 27 2026) lets new residential and light commercial split systems with GWP of 700 or more still be installed where all specified components were manufactured or imported before Jan 1 2025, with no end date. Servicing and repairing existing R-410A equipment remains legal. See the R-410A phase-out and the AIM Act rules for the full picture.
Two numbers sit close to the lines. R-32 (675) and R-513A (631) are under 700. R-449A (1,396.3 under 84.64) and R-448A (1,386.1) are under 1,400. EPA’s SNAP page rounds R-449A to 1,400, so use the 84.64 value when a limit is at stake.
Separately, the AIM Act phasedown caps HFC production and import on an exchange-value-weighted basis (40 CFR 84.7): 90% of baseline in 2022–2023, 60% in 2024–2028, 30% in 2029–2033, 20% in 2034–2035 and 15% from 2036. HFOs are not regulated substances under Part 84.
GWP chart: 62 refrigerants
Sorted from highest to lowest GWP. “GWP, AR4 basis” is the IPCC AR4 100-year value (mass-weighted for blends, with HFO constituents at the common industry values of 4 for R-1234yf and 6 for R-1234ze(E)). “EPA 40 CFR 84.64 value” is the figure EPA computes for Technology Transitions limits; a dash means the refrigerant has no Part 84 value. Safety classes are ASHRAE Standard 34.
| Refrigerant | Type | Safety class | GWP, AR4 basis | EPA 40 CFR 84.64 value | Note |
|---|---|---|---|---|---|
| R-23 | HFC | A1 | 14,800 | 14,800 | |
| R-508B | HFC/PFC | A1 | 13,396 | 6,808 | 84.64 counts only the HFC-23 share (PFC-116 has no value) |
| R-12 | CFC | A1 | 10,900 | — | CFC, ozone-depleting; no Part 84 value |
| R-500 | CFC/HFC azeotrope | A1 | 8,077 | 32.5 | 84.64 counts only the HFC-152a share |
| R-14 (tetrafluoromethane) | PFC | A1 | 7,390 | — | Perfluorocarbon; not an AIM Act regulated substance |
| R-113 | CFC | A1 | 6,130 | — | CFC, ozone-depleting; no Part 84 value |
| R-11 | CFC | A1 | 4,750 | — | CFC, ozone-depleting; no Part 84 value |
| R-502 | CFC | A1 | 4,657 | — | CFC/HCFC blend; no Part 84 value |
| R-143a | HFC | A2L | 4,470 | 4,470 | Blend component |
| R-507A | HFC | A1 | 3,985 | 3,985 | |
| R-404A | HFC | A1 | 3,922 | 3,921.6 | |
| R-125 | HFC | A1 | 3,500 | 3,500 | Blend component |
| R-434A (RS-45) | HFC/HC | A1 | 3,245 | 3,245.4 | |
| R-408A | HCFC/HFC blend | A1 | 3,152 | 2,301.2 | 84.64 does not count HCFC-22 |
| R-422A (MO79) | HFC/HC | A1 | 3,143 | 3,143 | |
| R-422D (MO29) | HFC/HC | A1 | 2,729 | 2,729 | R-600a counted at the 84.64 value |
| R-421A | HFC | A1 | 2,631 | 2,630.6 | |
| R-422B (NU-22B) | HFC/HC | A1 | 2,526 | 2,525.6 | R-600a counted at the 84.64 value |
| R-424A (RS-44) | HFC/HC | A1 | 2,440 | 2,439.6 | Isopentane excluded |
| R-417A | HFC/HC | A1 | 2,346 | 2,346.1 | R-600 counted at the 84.64 value |
| R-438A (MO99) | HFC/HC | A1 | 2,265 | 2,264.5 | R-600 counted at the 84.64 value; R-601a excluded |
| R-452A | HFC/HFO | A1 | 2,140 | 2,139.6 | HFO counted at the industry value |
| R-427A | HFC | A1 | 2,138 | 2,138.3 | |
| R-407A | HFC | A1 | 2,107 | 2,107 | |
| R-410A | HFC | A1 | 2,088 | 2,087.5 | |
| R-407F | HFC | A1 | 1,825 | 1,824.5 | |
| R-22 | HCFC | A1 | 1,810 | — | HCFC, ozone-depleting; no Part 84 value |
| R-437A | HFC/HC blend | A1 | 1,805 | 1,805.1 | Butane counted at the industry value; pentane excluded |
| R-407C | HFC | A1 | 1,774 | 1,773.9 | |
| R-453A (RS-70) | HFC/HC | A1 | 1,765 | 1,765.4 | R-600 counted at the 84.64 value; R-601a excluded |
| R-458A (TdX 20) | HFC | A1 | 1,650 | 1,650 | |
| R-409A | HCFC blend | A1 | 1,585 | — | HCFC blend; no Part 84 value |
| R-407H | HFC | A1 | 1,495 | 1,495.1 | |
| R-134a | HFC | A1 | 1,430 | 1,430 | |
| R-449A | HFC/HFO | A1 | 1,397 | 1,396.3 | HFO counted at the industry value |
| R-448A | HFC/HFO | A1 | 1,387 | 1,386.1 | HFO counted at the industry value |
| R-401B | HCFC blend | A1 | 1,288 | 13.6 | 84.64 counts only the HFC-152a share |
| R-401A | HCFC blend | A1 | 1,182 | 16.1 | 84.64 counts only the HFC-152a share |
| R-416A | HCFC/HFC blend | A1 | 1,084 | 843.8 | 84.64 does not count HCFC-124 |
| R-245fa | HFC | B1 | 1,030 | 1,030 | |
| R-452B | HFC/HFO | A2L | 698 | 697.5 | Just under the 700 limit on the EPA basis |
| R-32 | HFC | A2L | 675 | 675 | |
| R-513A | HFC/HFO | A1 | 631 | 629.8 | HFO counted at the industry value |
| R-450A | HFC/HFO blend | A1 | 604 | 601.2 | HFO counted at the industry value |
| R-454B | HFC/HFO | A2L | 466 | 465.4 | Commonly published as 466; EPA calculation gives 465 |
| R-515B | HFC/HFO | A1 | 292 | 287.5 | HFO counted at the industry value |
| R-454A | HFC/HFO | A2L | 239 | 236.9 | HFO counted at the industry value |
| R-454C | HFC/HFO | A2L | 148 | 145.9 | HFO counted at the industry value |
| R-455A | HFC/HFO | A2L | 148 | 145.9 | HFO counted at the industry value |
| R-152a | HFC | A2 | 124 | 124 | |
| R-123 | HCFC | B1 | 77 | — | HCFC; no Part 84 value |
| R-170 (ethane) | HC | A3 | Not in AR4 | 5.5 | Hydrocarbon; 84.64 value |
| R-1233zd(E) | HCFO | A1 | Not in AR4 | 4 | EPA SNAP chiller page lists 4.7-7 |
| R-290 (propane) | HC | A3 | Not in AR4 | 3.3 | Hydrocarbon; EPA SNAP pages list 3 |
| R-1336mzz(Z) | HFO | A1 | Not in AR4 | 2 | HFO; EPA SNAP chiller page lists 9 |
| R-1270 (propylene) | HC | A3 | Not in AR4 | 1.8 | Hydrocarbon; EPA SNAP pages list 1.8 or 5 |
| R-1234yf | HFO | A2L | Not in AR4 | 1 | HFO; EPA MVAC page lists 4; AR5 less than 1 |
| R-1234ze(E) | HFO | A2L | Not in AR4 | 1 | HFO; EPA SNAP chiller page lists 6; AR5 less than 1 |
| R-600a (isobutane) | HC | A3 | Not in AR4 | 1 | Hydrocarbon; EPA SNAP pages list 3 |
| R-717 (ammonia) | Natural | B2L | Not in AR4 | 1 | No IPCC value; EPA SNAP pages list 0 |
| R-744 (CO2) | Natural | A1 | 1 | 1 | Reference gas, 1 by definition |
| R-514A | HFO/HCO | B1 | Not in AR4 | — | Not an AIM Act regulated substance; EPA SNAP chiller page lists 7 |
Reading the chart
- Ozone-depleting refrigerants (R-11, R-12, R-113, R-22, R-123, R-502, R-500, R-401A, R-401B, R-408A, R-409A, R-416A) carry AR4 GWPs, but only their HFC share, if any, has a Part 84 value. They are controlled under 40 CFR 82, not the AIM Act.
- HFO, HCFO and natural refrigerants have no AR4 listing. Their EPA values come from 84.64 Table 1, and EPA’s program pages sometimes print different figures (for example 4 for R-1234yf on the MVAC page, 3 for propane on SNAP pages).
- Safety class matters as much as GWP. The R-410A replacements in new residential and light commercial AC, R-32 and R-454B, are both A2L. See A2L refrigerants for what changes in handling.
- GWP is not a retrofit guide. A lower-GWP refrigerant still has to suit the equipment, oil and safety listing. See the R-410A replacement and R-22 replacement pages, and refrigerant oil types for lubricant changes.
Related
Sources
- 40 CFR Part 84 Appendix A: Regulated substances and exchange values ecfr.gov
- 40 CFR 84.64: Global warming potentials (blend calculation and constituent values) ecfr.gov
- 40 CFR 84.54: Technology Transitions restrictions by sector ecfr.gov
- 40 CFR 84.7: HFC production and consumption phasedown schedule ecfr.gov
- 91 FR 31284 (May 26 2026): Reconsideration of Certain Technology Transitions Requirements, final rule federalregister.gov
- IPCC AR4 WG1 Chapter 2, Table 2.14 (100-year GWP) ipcc.ch
- IPCC AR5 WG1 Chapter 8, Appendix 8.A, Table 8.A.1 ipcc.ch
- IPCC AR6 WG1 Chapter 7 Supplementary Material, Table 7.SM.7 ipcc.ch
- EPA: MVAC acceptable refrigerants and their impacts epa.gov
- UNEP/ASHRAE Factsheet: Refrigerant designations and safety classifications (ASHRAE 34-2024) ashrae.org
Reviewed . Found an error? Tell us and we will correct it.