R-508B PT Chart and Refrigerant Profile

R-508B is an A1 HFC/PFC azeotropic blend of R-23 and R-116 (46/54 % by mass). At 40°F its vapor (dew) pressure is 448.7 psig; at 50°F its liquid (bubble) pressure is 519.5 psig.

Reviewed · PT values computed with CoolProp 8.0.0 and checked against a published chart (largest difference 1.5 psi)

R-508B at a glance

Safety class (ASHRAE 34)A1: lower toxicity, no flame propagation
TypeHFC/PFC, azeotropic blend
CompositionR-23 46% · R-116 54% by mass
GWP (100-year, AR4)13,396 · AR5: 11,698AR4 mass-weighted (EPA SNAP lists 13,396). The AIM Act exchange value counts only the HFC-23 part: 6,808.
Ozone depletion potential0
LubricantPOE (polyolester)
Boiling point at 14.7 psia-125.8°F bubble · -125.1°F dew
Critical point52.5°F, 554 psia
40°F evaporating448.7 psig (dew), glide 0.0°F
50°F condensing519.5 psig (bubble)
Charge asLiquid, as suppliers recommend for blends (an azeotrope barely fractionates)
Typical useLow stage of cascade systems; Ultra-low temperature freezers (about -40 to -150°F); Very low temperature process and test equipment
Trade namesFreon 95 (Chemours), Genetron 508B (Honeywell)
US statusContains regulated HFC-23 (AIM Act phasedown) plus PFC-116; SNAP-acceptable in very-low-temperature refrigeration since July 28 1995.
ReplacesR-13, R-503

R-508B gauge reading to saturation temperature

psig

°F

ft

40.0°F vapor (dew) saturation at 449 psig: use for suction and superheat 40.0°F liquid (bubble) saturation: use for the liquid line and subcooling

Enter a vacuum as a negative psig (−5 psig ≈ 10.2 in Hg). Gauges read relative to local air pressure, so above about 2,000 ft the elevation correction changes low-pressure readings noticeably. PT calculator for all refrigerants

R-508B PT chart (°F and psig)

R-508B is a blend, so it has two saturation pressures at each temperature. Read the vapor (dew) column against suction pressure for superheat and the liquid (bubble) column against liquid-line pressure for subcooling. Tap a row to load it into the lookup.

-130°F to 50°F · psig at sea level · °C and kPa in the CSV · italic = inches Hg vacuum

R-508B pressure-temperature chart, -130°F to 50°F
°FLiquidbubble psigVapordew psig
-1303.8″4.5″
-1293.0″3.6″
-1282.1″2.7″
-1271.2″1.8″
-1260.2″0.9″
-1250.40.1
-1240.90.5
-1231.41.0
-1221.91.6
-1212.42.1
-1202.92.6
-1193.53.2
-1184.13.7
-1174.64.3
-1165.24.9
-1155.85.5
-1146.46.1
-1137.16.8
-1127.77.4
-1118.48.1
-1109.18.8
-1099.89.5
-10810.510.2
-10711.210.9
-10611.911.7
-10512.712.4
-10413.513.2
-10314.314.0
-10215.114.8
-10115.915.6
-10016.716.5
-9917.617.3
-9818.518.2
-9719.419.1
-9620.320.0
-9521.221.0
-9422.221.9
-9323.222.9
-9224.223.9
-9125.224.9
-9026.226.0
-8927.327.0
-8828.328.1
-8729.429.2
-8630.530.3
-8531.731.5
-8432.832.6
-8334.033.8
-8235.235.0
-8136.536.3
-8037.737.5
-7939.038.8
-7840.340.1
-7741.641.4
-7642.942.8
-7544.344.1
-7445.745.5
-7347.146.9
-7248.648.4
-7150.049.9
-7051.551.4
-6953.052.9
-6854.654.4
-6756.156.0
-6657.757.6
-6559.459.2
-6461.060.9
-6362.762.6
-6264.464.3
-6166.166.0
-6067.967.8
-5969.769.6
-5871.571.4
-5773.473.3
-5675.375.2
-5577.277.1
-5479.179.0
-5381.181.0
-5283.183.0
-5185.185.0
-5087.287.1
-4989.389.2
-4891.491.3
-4793.693.5
-4695.895.7
-4598.097.9
-44100.3100.2
-43102.5102.5
-42104.9104.8
-41107.2107.2
-40109.6109.6
-39112.1112.0
-38114.5114.5
-37117.1117.0
-36119.6119.6
-35122.2122.2
-34124.8124.8
-33127.4127.4
-32130.1130.1
-31132.9132.8
-30135.6135.6
-29138.4138.4
-28141.3141.3
-27144.1144.1
-26147.1147.1
-25150.0150.0
-24153.0153.0
-23156.1156.1
-22159.2159.2
-21162.3162.3
-20165.4165.4
-19168.7168.7
-18171.9171.9
-17175.2175.2
-16178.5178.5
-15181.9181.9
-14185.3185.3
-13188.8188.8
-12192.3192.3
-11195.9195.9
-10199.5199.5
-9203.1203.1
-8206.8206.8
-7210.6210.6
-6214.4214.4
-5218.2218.2
-4222.1222.1
-3226.0226.0
-2230.0230.0
-1234.1234.0
0238.2238.1
1242.3242.3
2246.5246.4
3250.7250.7
4255.0255.0
5259.3259.3
6263.7263.7
7268.2268.1
8272.7272.6
9277.2277.2
10281.9281.8
11286.5286.5
12291.2291.2
13296.0296.0
14300.9300.8
15305.8305.7
16310.7310.6
17315.7315.6
18320.8320.7
19325.9325.8
20331.1331.0
21336.4336.3
22341.7341.6
23347.0347.0
24352.5352.4
25358.0357.9
26363.6363.5
27369.2369.1
28374.9374.8
29380.7380.6
30386.5386.4
31392.4392.3
32398.4398.3
33404.4404.3
34410.5410.4
35416.7416.6
36423.0422.9
37429.3429.2
38435.8435.7
39442.3442.2
40448.8448.7
41455.5455.4
42462.2462.1
43469.1469.0
44476.0475.9
45483.0482.9
46490.1490.0
47497.3497.2
48504.6504.5
49512.0511.9
50519.5519.4

Download the R-508B table as CSV

R-508B pressure-temperature curve from -130°F to 50°F, showing the bubble and dew lines
R-508B saturation pressure against temperature; the gap between the liquid and vapor lines is the glide.

Where you will find R-508B

R-508B is an ultra-low temperature refrigerant: an azeotrope of 46% R-23 and 54% R-116 by mass. Honeywell gives its range as roughly -40 to -101°C (-40 to -150°F). You find it in the low stage of cascade systems, chiefly ultra-low temperature freezers, and in other very low temperature process and test equipment. It replaced R-13 and R-503. EPA lists R-508B as acceptable in very-low-temperature refrigeration, for new and retrofit equipment, since July 28, 1995.

R-508B cannot condense against ambient air: its critical point is 52.5°F. A separate high stage condenses it in a cascade heat exchanger. The chart above stops at 50°F for that reason.

Compared with R-23, the other common low-stage refrigerant, R-508B runs at higher pressure at the same temperature, which means lower evaporating temperature at a given suction pressure. At -100°F R-508B reads 16.7 psig (bubble) against 9.0 psig for R-23. At -120°F it is still above atmospheric (2.9 psig bubble, 2.6 psig dew), where R-23 is in a vacuum.

A warm, idle low stage is near or above the critical temperature, so its standstill pressure is not a chart value. The system’s pressure rating has to cover it; never assume a stopped low stage sits at low pressure.

Charging R-508B

R-508B is an azeotrope, so its composition shifts very little between liquid and vapor. The chart shows bubble and dew columns because the blend model separates them slightly at the coldest temperatures (0.8°F glide at -130°F, essentially zero from -40°F up). For practical service it behaves like a single-component refrigerant. No manufacturer charging statement is quoted here; where the nameplate gives a charge weight, weigh it in to that number.

For superheat on the low stage, read suction pressure against the dew column and use the superheat calculator; the PT calculator converts any pressure to saturation temperature. The how to read a PT chart guide covers bubble and dew columns. Check the pressure rating of gauges, hoses and recovery cylinders before connecting to a warm circuit.

Oil and compatibility

BITZER lists POE for R-508B and notes that polyol ester oils are suitable for R-508A/B but must be matched to the special requirements of very low temperature operation. Use the compressor maker’s specified oil. The refrigerant oil types guide explains POE.

Safety, handling and recovery

A1 under ASHRAE 34: lower toxicity, no flame propagation. For Section 608, R-508B is a very-high-pressure refrigerant (critical temperature below 104°F; 40 CFR 82.152 names it as an example), so the work is Type II or Universal.

It is a non-exempt refrigerant: no venting, recovery to 0 in Hg for very-high-pressure appliances (40 CFR 82.156 Table 1), and sales restricted to certified technicians since January 1, 2018 (40 CFR 82.154(c)). Recover into a cylinder rated for the pressure.

Cylinders: R-508B’s legacy color was dark blue. Since January 1, 2020 new containers are light green-gray RAL 7044 under AHRI Guideline N-2017, with the legacy color kept on the label. See cylinder colors.

Status and replacements

R-508B has two GWP figures, and the difference matters. The full climate figure on the AR4 basis is 13,396 (46% × 14,800 for R-23 plus 54% × 12,200 for R-116), which is also what EPA’s SNAP page lists. For AIM Act allowance accounting only the HFC part counts: R-116 is a perfluorocarbon, not an AIM Act regulated substance, so the exchange value is 6,808 (46% × 14,800). The R-23 content is subject to the HFC phasedown (40 CFR 84.7): allowances at 60% of baseline in 2024–2028, 30% in 2029–2033, 20% in 2034–2035 and 15% from 2036.

No Technology Transitions sector limit for very-low-temperature equipment was found in 40 CFR 84.54. HFC leak repair under 40 CFR 84.106 applies from January 1, 2026 to appliances with 15 lb or more of HFC; many ultra-low freezers hold less, so check the nameplate charge.

No direct replacement is listed in the sources used for this page. EPA’s very-low-temperature list also includes R-508A, ethane (R-170, A3, acceptable with use conditions) and R-744. For R-23 alternatives see the R-23 profile; for GWPs see the GWP chart.

Common questions

What is the difference between R-508B and R-23?

R-23 is a single HFC; R-508B is an azeotrope of 46% R-23 and 54% R-116. R-508B runs at higher pressure at the same temperature and has a lower critical point (52.5°F against 79.1°F), and its AIM Act exchange value is lower because R-116 is not counted.

How this chart was computed

Every pressure on this page is calculated, not copied: CoolProp 8.0.0 (HEOS backend), the open-source implementation of the reference equations of state, using the model mix:R508B at the nominal ASHRAE 34 composition. Gauge values assume sea-level air pressure (14.696 psia); kPa values in the CSV are absolute.

Spot check against National Refrigerants Refrigerant Reference Guide, 7th Edition 2020: R-508B:

°FColumnPublishedThis chartDifference
-100bubble31.0 psia31.4 psia+0.4 psi
-100dew30.8 psia31.2 psia+0.4 psi
-60bubble81.6 psia82.6 psia+1.0 psi
-60dew81.5 psia82.5 psia+1.0 psi
-40bubble122.8 psia124.3 psia+1.5 psi
-40dew122.8 psia124.3 psia+1.5 psi

Only one reference found (NRI, basis not stated, psia to 0.1). Deviation grows to 1.5 psi (1.2%) at -40 °F; within about 1% over -100 to -60 °F. Borderline; treated as ok.

Charts from different publishers can differ by a few tenths of a psi because of the equation of state and blend tolerances. Always charge to the equipment manufacturer's data. Full method and every spot check

Calculators for R-508B

Sources

  1. Honeywell Genetron 508B product page advancedmaterials.honeywell.com
  2. Chemours Freon 95 (R-508B) product page freon.com
  3. BITZER Refrigerant Report: VLT refrigerants bitzer.de
  4. EPA SNAP: Substitutes in Very Low Temperature Refrigeration epa.gov
  5. eCFR 40 CFR 84.64: GWPs and exchange values for blends ecfr.gov
  6. eCFR 40 CFR 84.7: HFC phasedown schedule ecfr.gov
  7. eCFR 40 CFR 82.152: Section 608 definitions and pressure classes ecfr.gov

Reviewed . Found an error? Tell us and we will correct it.