R-125 PT Chart and Refrigerant Profile

R-125 is an A1 HFC single-component refrigerant. It saturates at 97.0 psig at 40°F and 261.4 psig at 100°F.

Reviewed · PT values computed with CoolProp 8.0.0 and checked against NIST reference data (largest difference 0.0 psi)

R-125 at a glance

Safety class (ASHRAE 34)A1: lower toxicity, no flame propagation
TypeHFC, single-component refrigerant
GWP (100-year, AR4)3,500 · AR5: 3,170AIM Act exchange value 3,500 (40 CFR 84 Appendix A)
Ozone depletion potential0
LubricantPOE or PVE (AB per BITZER)
Boiling point at 14.7 psia-54.6°F
Critical point150.8°F, 525 psia
40°F evaporating97.0 psig
100°F condensing261.4 psig
Charge asVapor or liquid
Typical useComponent of R-404A, R-507A, R-410A, R-407C and most R-22 and R-502 service blends; Total-flooding clean-agent fire suppression (FE-25, ECARO-25)
Trade namesFE-25 (Chemours; fire suppression), ECARO-25 (Fike; fire suppression)
US statusRegulated HFC under the AIM Act phasedown (exchange value 3,500); used mainly as a blend component; SNAP-acceptable as a fire suppression agent since 1994.

R-125 gauge reading to saturation temperature

psig

°F

ft

40.0°F saturation temperature at 97 psig

Enter a vacuum as a negative psig (−5 psig ≈ 10.2 in Hg). Gauges read relative to local air pressure, so above about 2,000 ft the elevation correction changes low-pressure readings noticeably. PT calculator for all refrigerants

R-125 PT chart (°F and psig)

R-125 is a single-component refrigerant, so one pressure applies at each temperature for both the evaporator and the condenser. Tap a row to load it into the lookup.

-40°F to 148°F · psig at sea level · °C and kPa in the CSV · italic = inches Hg vacuum

R-125 pressure-temperature chart, -40°F to 148°F
°Fpsig
-406.8
-397.4
-387.9
-378.5
-369.1
-359.7
-3410.3
-3310.9
-3211.5
-3112.1
-3012.8
-2913.4
-2814.1
-2714.8
-2615.5
-2516.2
-2416.9
-2317.6
-2218.4
-2119.1
-2019.9
-1920.7
-1821.5
-1722.3
-1623.1
-1524.0
-1424.8
-1325.7
-1226.6
-1127.5
-1028.4
-929.4
-830.3
-731.3
-632.2
-533.2
-434.2
-335.3
-236.3
-137.4
038.4
139.5
240.6
341.8
442.9
544.1
645.2
746.4
847.6
948.9
1050.1
1151.4
1252.7
1354.0
1455.3
1556.6
1658.0
1759.4
1860.8
1962.2
2063.6
2165.1
2266.6
2368.1
2469.6
2571.2
2672.7
2774.3
2875.9
2977.5
3079.2
3180.9
3282.6
3384.3
3486.0
3587.8
3689.6
3791.4
3893.2
3995.1
4097.0
4198.9
42100.8
43102.7
44104.7
45106.7
46108.7
47110.8
48112.9
49115.0
50117.1
51119.3
52121.5
53123.7
54125.9
55128.2
56130.4
57132.8
58135.1
59137.5
60139.9
61142.3
62144.8
63147.2
64149.8
65152.3
66154.9
67157.5
68160.1
69162.8
70165.5
71168.2
72170.9
73173.7
74176.5
75179.4
76182.3
77185.2
78188.1
79191.1
80194.1
81197.1
82200.2
83203.3
84206.4
85209.6
86212.8
87216.0
88219.3
89222.6
90226.0
91229.4
92232.8
93236.2
94239.7
95243.2
96246.8
97250.4
98254.0
99257.7
100261.4
101265.1
102268.9
103272.8
104276.6
105280.5
106284.5
107288.4
108292.5
109296.5
110300.6
111304.8
112309.0
113313.2
114317.5
115321.8
116326.1
117330.6
118335.0
119339.5
120344.0
121348.6
122353.2
123357.9
124362.6
125367.4
126372.2
127377.1
128382.0
129387.0
130392.0
131397.1
132402.2
133407.4
134412.6
135417.9
136423.2
137428.6
138434.0
139439.5
140445.1
141450.8
142456.4
143462.2
144468.0
145473.9
146479.9
147486.0
148492.1

Download the R-125 table as CSV

R-125 pressure-temperature curve from -40°F to 148°F
R-125 saturation pressure against temperature.

Where you will find R-125

R-125 (HFC-125, pentafluoroethane) is rarely the refrigerant on a nameplate. You meet it inside blends. It is the nonflammable, higher-pressure component in most HFC mixes:

Blend R-125 by mass Main use
R-422A (MO79) 85.1% R-22/R-502 refrigeration retrofit
R-422D (MO29) 65.1% R-22 retrofit
R-404A 44% Commercial refrigeration
R-507A 50% Commercial refrigeration
R-410A 50% Residential AC and heat pumps
R-407A 40% Commercial refrigeration
R-448A 26% Commercial refrigeration
R-407C 25% AC, R-22 replacement
R-407H 15% Commercial refrigeration
R-452B 7% New A2L AC and heat pumps

It also carries much of each blend’s GWP. At 3,500 it is well above R-32 (675) and R-134a (1,430); in R-410A, the 50% R-125 share accounts for 1,750 of the 2,088 total. The GWP chart shows the effect across blends.

Outside blends, pure HFC-125 is best known as a fire suppression agent. EPA SNAP has listed HFC-125 (FE-25, MH125) as an acceptable total-flooding agent since March 18 1994, for use per NFPA 2001, and NAF S-125 (HFC-125 with 0.1% d-limonene) since Aug 21 2003. A-Gas supplies it for data centers, telecom sites, aviation, maritime, museums and power plants. Those are fire-protection systems, not refrigeration circuits.

Handling and charging pure R-125

As a single-component refrigerant, R-125 has no glide and does not fractionate, so it can be moved as vapor or liquid. One pressure applies at each temperature: 97.0 psig at 40°F and 261.4 psig at 100°F on this chart.

We found no manufacturer charging guidance for systems running on neat R-125, and it does not appear on EPA’s refrigeration end-use pages we checked. Use the PT chart above as a reference, for example to identify a cylinder by its standing pressure, not as a charging target.

Do not try to “correct” a leaked blend by adding pure R-125. Blend composition is held to tight tolerances under AHRI Standard 700; R-422A, for example, must contain 84.1–86.1% R-125. A gauge reading cannot confirm the mix, so a fractionated or contaminated charge gets recovered and replaced with the blend itself.

Oil and compatibility

BITZER lists POE, PVE and AB for R-125. In practice the oil follows the blend and the compressor, not the component: R-404A and R-410A systems run POE, while some R-22 retrofit blends with R-125 also run with mineral oil or AB. Check the compressor maker’s approval for the specific blend. See the refrigerant oil guide.

Safety, handling and recovery

R-125 is A1: lower toxicity, no flame propagation. It is a Section 608 high-pressure refrigerant. Its liquid saturation pressure at 104°F is 291.3 psia (276.6 psig), inside the 170–355 psia band, and its critical temperature is above 104°F, so it is not very-high-pressure.

Venting is prohibited. Type II or Universal certification covers refrigeration appliances that use it, and sales of HFC refrigerants have been limited to certified technicians since Jan 1 2018. Recover high-pressure appliances made after Nov 15 1993 to 0 in Hg under 200 lb of charge and 10 in Hg at 200 lb or more (refrigerant recovery).

The legacy label color for R-125 in AHRI Guideline N-2017 Table 1 is medium brown (tan), PMS 465. R-407C is also medium brown, so read the label, not the paint. New cylinders since Jan 1 2020 are light green-gray (RAL 7044) (cylinder colors).

Status

HFC-125 is a regulated substance under the AIM Act with an exchange value of 3,500 (40 CFR 84 Appendix A). Production and import allowances are 60% of baseline in 2024–2028, 30% in 2029–2033, 20% in 2034–2035 and 15% from 2036. The phasedown counts the R-125 in every blend above, so it bears on the supply of R-404A, R-507A, R-410A and the R-22 drop-ins.

As a neat refrigerant its GWP is above every Technology Transitions limit for new systems. Servicing existing equipment with R-125 blends remains legal. For blends that cut R-125 content, see R-404A replacement and R-410A replacement.

How this chart was computed

Every pressure on this page is calculated, not copied: CoolProp 8.0.0 (HEOS backend), the open-source implementation of the reference equations of state, using the model pure:R125. Gauge values assume sea-level air pressure (14.696 psia); kPa values in the CSV are absolute.

Spot check against NIST Chemistry WebBook, SRD 69, Thermophysical Properties of Fluid Systems: R125, saturation properties (temperature increments):

°FColumnPublishedThis chartDifference
-40saturation21.5 psia21.5 psia0.0 psi
0saturation53.1 psia53.1 psia0.0 psi
40saturation111.6 psia111.6 psia0.0 psi
120saturation358.7 psia358.7 psia0.0 psi

NIST WebBook implements the same reference equation of state as CoolProp, so near-zero deviation there confirms the implementation and unit handling. No manufacturer chart was checked. Table stops at 148 °F (critical point 150.8 °F).

Charts from different publishers can differ by a few tenths of a psi because of the equation of state and blend tolerances. Always charge to the equipment manufacturer's data. Full method and every spot check

Calculators for R-125

Sources

  1. BITZER Refrigerant Report: refrigerant data table bitzer.de
  2. EPA SNAP: Substitutes in total flooding agents epa.gov
  3. A-Gas: HFC-125 fire protection agent agas.com
  4. 40 CFR Part 84 Appendix A: regulated substances and exchange values ecfr.gov
  5. AHRI Standard 700-2017 with Addendum 1: Specifications for Refrigerants (A-Gas copy) agas.com
  6. AHRI Guideline N-2017: Assignment of Refrigerant Container Colors (Wayback copy) web.archive.org

Reviewed . Found an error? Tell us and we will correct it.

More in Commercial refrigeration