R-407H PT Chart and Refrigerant Profile

R-407H is an A1 HFC zeotropic blend of R-32, R-125 and R-134a (32.5/15/52.5 % by mass). At 40°F its vapor (dew) pressure is 66.4 psig; at 100°F its liquid (bubble) pressure is 235.2 psig.

Reviewed · PT values computed with CoolProp 8.0.0 and checked against a published chart (largest difference 0.0 psi)

R-407H at a glance

Safety class (ASHRAE 34)A1: lower toxicity, no flame propagation
TypeHFC, zeotropic blend
CompositionR-32 32.5% · R-125 15% · R-134a 52.5% by mass
GWP (100-year, AR4)1,495 · AR5: 1,378EPA's 40 CFR 84.64 calculation gives 1,495.1.
Ozone depletion potential0
LubricantPOE (PVE also compatible; no mineral oil)
Boiling point at 14.7 psia-48.3°F bubble · -35.6°F dew
Critical point187.7°F, 704 psia
40°F evaporating66.4 psig (dew), glide 11.1°F
100°F condensing235.2 psig (bubble), glide 9.1°F
Charge asLiquid only (blend can fractionate as vapor)
Typical useWalk-in coolers and freezers; Supermarket racks and display cases, remote condensing units; Truck and trailer refrigeration; R-404A, R-507A and R-22 retrofits
Trade namesCreard R-407H (Daikin America), D407 (Daikin; name used by EPA)
US statusSNAP-acceptable in retail food and transport refrigeration (2017, 2019); GWP 1,495 is above the 1,400 limits for new remote condensing units (2026) and supermarket systems (2027).
ReplacesR-404A, R-507A, R-22

R-407H gauge reading to saturation temperature

psig

°F

ft

39.7°F vapor (dew) saturation at 66 psig: use for suction and superheat 28.6°F liquid (bubble) saturation: use for the liquid line and subcooling

Enter a vacuum as a negative psig (−5 psig ≈ 10.2 in Hg). Gauges read relative to local air pressure, so above about 2,000 ft the elevation correction changes low-pressure readings noticeably. PT calculator for all refrigerants

R-407H PT chart (°F and psig)

R-407H is a blend, so it has two saturation pressures at each temperature. Read the vapor (dew) column against suction pressure for superheat and the liquid (bubble) column against liquid-line pressure for subcooling. Tap a row to load it into the lookup.

-40°F to 150°F · psig at sea level · °C and kPa in the CSV · italic = inches Hg vacuum

R-407H pressure-temperature chart, -40°F to 150°F
°FLiquidbubble psigVapordew psig
-403.63.4″
-394.02.6″
-384.51.9″
-375.01.1″
-365.50.3″
-356.00.3
-346.60.7
-337.11.1
-327.61.5
-318.22.0
-308.72.4
-299.32.9
-289.93.3
-2710.53.8
-2611.14.3
-2511.74.8
-2412.45.3
-2313.05.8
-2213.76.4
-2114.36.9
-2015.07.4
-1915.78.0
-1816.48.6
-1717.19.2
-1617.99.8
-1518.610.4
-1419.411.0
-1320.111.6
-1220.912.3
-1121.712.9
-1022.513.6
-923.414.3
-824.214.9
-725.015.6
-625.916.4
-526.817.1
-427.717.8
-328.618.6
-229.519.4
-130.520.2
031.421.0
132.421.8
233.422.6
334.423.4
435.424.3
536.425.2
637.526.0
738.626.9
839.627.9
940.728.8
1041.929.7
1143.030.7
1244.231.7
1345.332.7
1446.533.7
1547.734.7
1648.935.8
1750.236.8
1851.537.9
1952.739.0
2054.040.1
2155.341.3
2256.742.4
2358.043.6
2459.444.8
2560.846.0
2662.247.2
2763.748.4
2865.149.7
2966.651.0
3068.152.3
3169.653.6
3271.155.0
3372.756.3
3474.357.7
3575.959.1
3677.560.5
3779.162.0
3880.863.4
3982.564.9
4084.266.4
4185.967.9
4287.769.5
4389.571.1
4491.372.7
4593.174.3
4695.075.9
4796.877.6
4898.779.3
49100.681.0
50102.682.7
51104.684.5
52106.686.2
53108.688.0
54110.689.9
55112.791.7
56114.893.6
57116.995.5
58119.097.4
59121.299.4
60123.4101.4
61125.6103.4
62127.9105.4
63130.2107.5
64132.5109.6
65134.8111.7
66137.2113.8
67139.6116.0
68142.0118.2
69144.4120.4
70146.9122.6
71149.4124.9
72151.9127.2
73154.5129.6
74157.1131.9
75159.7134.3
76162.3136.7
77165.0139.2
78167.7141.7
79170.4144.2
80173.2146.7
81176.0149.3
82178.8151.9
83181.7154.6
84184.6157.2
85187.5159.9
86190.4162.7
87193.4165.4
88196.4168.2
89199.5171.1
90202.6173.9
91205.7176.8
92208.8179.8
93212.0182.7
94215.2185.7
95218.5188.8
96221.8191.8
97225.1194.9
98228.4198.1
99231.8201.2
100235.2204.5
101238.7207.7
102242.2211.0
103245.7214.3
104249.2217.7
105252.8221.1
106256.5224.5
107260.1228.0
108263.8231.5
109267.6235.0
110271.4238.6
111275.2242.3
112279.0245.9
113282.9249.6
114286.8253.4
115290.8257.2
116294.8261.0
117298.8264.9
118302.9268.8
119307.1272.7
120311.2276.7
121315.4280.8
122319.7284.9
123323.9289.0
124328.3293.2
125332.6297.4
126337.0301.6
127341.5306.0
128345.9310.3
129350.5314.7
130355.0319.2
131359.6323.6
132364.3328.2
133369.0332.8
134373.7337.4
135378.5342.1
136383.3346.8
137388.2351.6
138393.1356.5
139398.1361.3
140403.1366.3
141408.1371.3
142413.2376.3
143418.3381.4
144423.5386.6
145428.8391.8
146434.0397.0
147439.4402.3
148444.7407.7
149450.1413.1
150455.6418.6

Download the R-407H table as CSV

R-407H pressure-temperature curve from -40°F to 150°F, showing the bubble and dew lines
R-407H saturation pressure against temperature; the gap between the liquid and vapor lines is the glide.

Where you will find R-407H

R-407H is a Daikin blend of R-32, R-125 and R-134a, sold in the US as Creard R-407H; EPA’s SNAP rules call it D407. Daikin America markets it as a replacement for R-404A and as an R-22 retrofit. Its promo sheet lists walk-in coolers and freezers, supermarket systems and display cases, transport refrigeration, remote condensing units and chillers. BITZER also lists it as a substitute for R-507A, R-407A and R-407F.

Expect it in converted R-404A walk-ins and racks, truck and trailer units, and some R-22 refrigeration conversions. Read the retrofit label; the nameplate keeps the original refrigerant. Daikin’s data sheet lists 25 lb disposable and 100 lb returnable containers. The legacy label color under AHRI Guideline N-2017 is light purple (wisteria, PMS 2573), not to be confused with R-502’s light purple (lavender).

It is a sibling of R-407A, R-407C and R-407F: same three components, different proportions. R-407H has the most R-32 of the four (32.5%) and the least R-125 (15%), which is how it gets a lower GWP.

Charging R-407H

Charge from the liquid phase only, and keep liquid out of the compressor, per Daikin’s R-22 retrofit guidelines.

The glide is large: 11.1°F at a 40°F dew point and 9.1°F at a 100°F bubble point. At 40°F this chart gives 66.4 psig dew and 84.2 psig bubble. Against R-404A (85.4 psig dew at 40°F), suction pressure at the same evaporator dew point is much lower, while condensing pressure is almost the same: 235.2 psig bubble at 100°F versus 236.8 psig. Do not set an R-404A system’s controls from habit after conversion.

Daikin’s charge guidance when replacing R-22:

  • Optimum charge is +8% to -2% of the R-22 charge.
  • With a receiver, fill to 90% of the nameplate liquid volume, then adjust.
  • Without a receiver, fill to 95% of the R-22 removed, then add small liquid increments while adjusting.

For low-temperature R-22 retrofits, Daikin allows R-407H only with liquid injection or another way to control discharge temperature. The temperature glide calculator shows the gap at any pressure.

Oil and compatibility

Daikin says R-407H is compatible with POE and PVE and recommends POE because it is widely available. It is not compatible with mineral oil, so all mineral oil must be removed when converting an R-22 system. BITZER lists POE and PVE, with AB only “with limitations”. Copeland AE 93-11 approves POE-32 for R-407H in Discus semi-hermetics and ZB/ZF scrolls on refrigerated rack retrofits.

An R-404A or R-507A system already runs POE, so the oil normally stays. Replace the filter-drier, evacuate to the OEM target (evacuation guide) and keep POE containers sealed against moisture. See the refrigerant oil guide.

Safety, handling and recovery

R-407H is A1: lower toxicity, no flame propagation. It is a Section 608 high-pressure refrigerant, with a computed liquid saturation pressure at 104°F of 263.9 psia (249.2 psig, bubble). Type II or Universal certification covers it, and sales have been limited to certified technicians since Jan 1 2018.

Recover appliances made after Nov 15 1993 to 0 in Hg under 200 lb of charge and 10 in Hg at 200 lb or more (refrigerant recovery). From Jan 1 2026, appliances holding 15 lb or more of HFC fall under the HFC leak repair rule (leak repair rules). New cylinders since Jan 1 2020 are light green-gray (RAL 7044).

Status and replacements

EPA SNAP lists R-407H as acceptable, retrofit and new, in:

  • remote condensing units, July 21 2017 (82 FR 33809)
  • supermarket systems, refrigerated food processing and dispensing, and truck and trailer transport refrigeration, Nov 25 2019 (84 FR 64765)

Its AR4 GWP of about 1,495 is less than half of R-404A’s 3,922, but it is above the interim 1,400 limits in 40 CFR 84.54 for new remote condensing units (from July 27 2026) and new supermarket systems (from Jan 1 2027). 84.54 also names it for new food processing and dispensing equipment (Jan 1 2027) and UL 621 ice cream makers (Jan 1 2028). Retrofitting and servicing existing systems remain legal. From Jan 1 2029, supermarket systems and refrigerated transport must be serviced with reclaimed HFC.

No source names a successor. Compare it with other R-404A options in R-404A replacement and with R-22 options in R-22 replacement.

Common questions

R-407H vs R-407C: what is the difference?

Both blend R-32, R-125 and R-134a, but R-407H carries 32.5/15/52.5 and R-407C 23/25/52. R-407H runs higher pressures (66.4 against 63.2 psig dew at 40°F) and has a lower GWP (1,495 against 1,774). R-407C is the AC refrigerant; R-407H is aimed at commercial refrigeration.

Is R-407H a drop-in for R-404A?

Daikin markets it as an R-404A replacement. It keeps POE oil, but the 11°F glide and lower suction pressure mean you should expect to adjust the charge, superheat and pressure controls. Treat it as a retrofit: recover the R-404A first, never top off with it.

How this chart was computed

Every pressure on this page is calculated, not copied: CoolProp 8.0.0 (HEOS backend), the open-source implementation of the reference equations of state, using the model mix:R407H at the nominal ASHRAE 34 composition. Gauge values assume sea-level air pressure (14.696 psia); kPa values in the CSV are absolute.

Spot check against Daikin Chemical Europe GmbH, R407H Product information, saturation table (based on REFPROP 9.0); no document number or date printed:

°FColumnPublishedThis chartDifference
-0.4bubble315.3 kPa315.3 kPa0.0 psi
-0.4dew243.5 kPa243.5 kPa0.0 psi
39.2bubble672.4 kPa672.4 kPa0.0 psi
39.2dew550.9 kPa550.9 kPa0.0 psi
100.4bubble1,732.6 kPa1,732.6 kPa0.0 psi
100.4dew1,519.9 kPa1,519.9 kPa0.0 psi

Within 0.005 psi of the Daikin table (REFPROP 9.0), i.e. CoolProp's R-32/R-125/R-134a parameters reproduce REFPROP exactly for this blend.

Charts from different publishers can differ by a few tenths of a psi because of the equation of state and blend tolerances. Always charge to the equipment manufacturer's data. Full method and every spot check

Calculators for R-407H

Sources

  1. Daikin America: R-404A and R-22 replacement (R-407H) daikin-america.com
  2. Daikin America: Creard R-407H technical data sheet daikin-america.com
  3. Daikin America: guidelines for using R-407H as an R-22 replacement daikin-america.com
  4. Copeland AE Bulletin 93-11: Refrigerants and lubricants approved for Copeland compressors webapps.copeland.com
  5. 82 FR 33809 (July 21 2017): SNAP listings including R-407H in remote condensing units govinfo.gov
  6. 84 FR 64765 (Nov 25 2019): SNAP listings including R-407H in supermarkets, food processing and transport govinfo.gov
  7. 40 CFR 84.54: Technology Transitions restrictions by sector ecfr.gov
  8. BITZER Refrigerant Report: refrigerant data table bitzer.de

Reviewed . Found an error? Tell us and we will correct it.

More in Commercial refrigeration