HVAC PT Data

Pressure-temperature charts, field calculators and refrigerant data for HVAC/R technicians

PT data: CoolProp 8.0 equations of state, US units

R-401B PT Chart and Refrigerant Profile

R-401B is an A1 HCFC blend zeotropic blend of R-22, R-152a and R-124 (61/11/28 % by mass). At 40°F its vapor (dew) pressure is 39.8 psig; at 100°F its liquid (bubble) pressure is 152.0 psig.

Reviewed · PT values computed with CoolProp 8.0.0 and checked against a published chart (largest difference 3.5 psi)

R-401B at a glance

Safety class (ASHRAE 34)A1: lower toxicity, no flame propagation
TypeHCFC blend, zeotropic blend
CompositionR-22 61% · R-152a 11% · R-124 28% by mass
GWP (100-year, AR4)1,288 · AR5: 1,236Counts all three components. EPA's 40 CFR 84.64 value is 13.6 because only the HFC-152a share is counted.
Ozone depletion potential0.04
LubricantMineral oil, alkylbenzene (AB) or POE
Boiling point at 14.7 psia-30.4°F bubble · -19.8°F dew
Critical point223.8°F, 687 psia
40°F evaporating39.8 psig (dew), glide 9.6°F
100°F condensing152.0 psig (bubble), glide 8.1°F
Charge asLiquid only (blend can fractionate as vapor)
Typical useR-12 retrofit in low-temperature equipment (domestic and commercial freezers, transport refrigeration); R-500 retrofit service
Trade namesFreon MP66 (Chemours), Suva MP66 (legacy DuPont name)
US statusHCFC service blend; HCFC-22 production and import ended Jan 1 2020 and HCFC-124 allowances reach zero in 2030, so supply is recovered or remaining stock.
ReplacesR-12, R-500
Replaced byR-437A, R-450A

R-401B gauge reading to saturation temperature

psig

°F

ft

40.2°F vapor (dew) saturation at 40 psig: use for suction and superheat 30.6°F liquid (bubble) saturation: use for the liquid line and subcooling

Enter a vacuum as a negative psig (−5 psig ≈ 10.2 in Hg). Gauges read relative to local air pressure, so above about 2,000 ft the elevation correction changes low-pressure readings noticeably. PT calculator for all refrigerants

R-401B PT chart (°F and psig)

R-401B is a blend, so it has two saturation pressures at each temperature. Read the vapor (dew) column against suction pressure for superheat and the liquid (bubble) column against liquid-line pressure for subcooling. Tap a row to load it into the lookup.

-40°F to 150°F · psig at sea level · °C and kPa in the CSV · italic = inches Hg vacuum

R-401B pressure-temperature chart, -40°F to 150°F
°FLiquidbubble psigVapordew psig
-406.5″12.5″
-395.9″12.0″
-385.3″11.5″
-374.6″11.0″
-364.0″10.4″
-353.3″9.9″
-342.6″9.3″
-331.9″8.8″
-321.2″8.2″
-310.4″7.6″
-300.27.0″
-290.56.4″
-280.95.7″
-271.35.1″
-261.74.4″
-252.13.7″
-242.53.0″
-232.92.3″
-223.41.6″
-213.80.9″
-204.20.1″
-194.70.3
-185.20.7
-175.61.1
-166.11.5
-156.61.9
-147.12.3
-137.62.7
-128.13.2
-118.63.6
-109.24.1
-99.74.5
-810.25.0
-710.85.4
-611.45.9
-512.06.4
-412.56.9
-313.17.4
-213.88.0
-114.48.5
015.09.0
115.69.6
216.310.1
317.010.7
417.611.3
518.311.9
619.012.5
719.713.1
820.413.7
921.214.3
1021.915.0
1122.715.6
1223.416.3
1324.216.9
1425.017.6
1525.818.3
1626.619.0
1727.419.7
1828.320.5
1929.121.2
2030.022.0
2130.922.7
2231.823.5
2332.724.3
2433.625.1
2534.525.9
2635.426.8
2736.427.6
2837.428.5
2938.429.3
3039.330.2
3140.431.1
3241.432.0
3342.432.9
3443.533.9
3544.634.8
3645.635.8
3746.736.8
3847.937.8
3949.038.8
4050.139.8
4151.340.8
4252.541.9
4353.742.9
4454.944.0
4556.145.1
4657.346.2
4758.647.4
4859.948.5
4961.149.7
5062.550.8
5163.852.0
5265.153.3
5366.554.5
5467.855.7
5569.257.0
5670.658.3
5772.159.5
5873.560.9
5975.062.2
6076.563.5
6178.064.9
6279.566.3
6381.067.7
6482.669.1
6584.170.5
6685.772.0
6787.373.5
6889.075.0
6990.676.5
7092.378.0
7194.079.5
7295.781.1
7397.482.7
7499.184.3
75100.985.9
76102.787.6
77104.589.3
78106.390.9
79108.292.6
80110.094.4
81111.996.1
82113.897.9
83115.899.7
84117.7101.5
85119.7103.3
86121.7105.2
87123.7107.1
88125.8109.0
89127.8110.9
90129.9112.8
91132.0114.8
92134.1116.8
93136.3118.8
94138.5120.8
95140.7122.9
96142.9125.0
97145.1127.1
98147.4129.2
99149.7131.4
100152.0133.6
101154.4135.8
102156.7138.0
103159.1140.2
104161.5142.5
105164.0144.8
106166.4147.1
107168.9149.5
108171.4151.9
109174.0154.3
110176.5156.7
111179.1159.1
112181.7161.6
113184.4164.1
114187.0166.6
115189.7169.2
116192.4171.8
117195.2174.4
118197.9177.0
119200.7179.7
120203.6182.4
121206.4185.1
122209.3187.9
123212.2190.7
124215.1193.5
125218.1196.3
126221.1199.2
127224.1202.1
128227.1205.0
129230.2207.9
130233.3210.9
131236.4213.9
132239.6217.0
133242.8220.0
134246.0223.1
135249.2226.3
136252.5229.4
137255.8232.6
138259.2235.9
139262.5239.1
140265.9242.4
141269.3245.7
142272.8249.1
143276.3252.5
144279.8255.9
145283.4259.4
146286.9262.8
147290.5266.4
148294.2269.9
149297.9273.5
150301.6277.1

Download the R-401B table as CSV

R-401B pressure-temperature curve from -40°F to 150°F, showing the bubble and dew lines
R-401B saturation pressure against temperature; the gap between the liquid and vapor lines is the glide.

Where you will find R-401B

R-401B is the low-temperature sister of R-401A. Both are HCFC service blends of R-22, R-152a and R-124, sold by DuPont as Suva MP66 and MP39 (now Chemours; R-401B is sold as Freon MP66). R-401B carries more R-22, which raises its capacity. DuPont’s ART-36 retrofit guide places it in R-12 systems running at low evaporator temperatures (below about -15°F) that need extra capacity, and in existing R-500 systems.

In practice that means domestic and commercial freezers and transport refrigeration. EPA’s SNAP program listed it as an R-12 substitute on Jan 13 1995 across household refrigerators and freezers, ice machines, supermarket and stand-alone equipment, vending, cold storage and transport. Copeland lists it for low- and medium-temperature work “for service applications only”.

Look for a retrofit tag reading R-401B or MP66 on a system whose compressor and nameplate say R-12 or R-500. The legacy cylinder color assigned in AHRI Guideline N-2017 was yellow-brown (mustard). Containers made since 2020 are light green-gray for every refrigerant, so read the label. R-401A and R-401B share components but not proportions, and their PT tables differ.

Charging R-401B

R-401B is a zeotropic blend. The computed glide at 40°F evaporating is 9.6°F, and it shrinks a little as pressure rises.

Charge liquid only. ART-36 says to take liquid only from the cylinder. Vapor charging pulls the lighter components first and leaves the system and the cylinder off-blend. Meter the liquid in slowly so it flashes before reaching the compressor.

Size the charge per the retrofit guide. ART-36 puts the best charge for an R-12 conversion at usually 75-90% of the original R-12 charge by weight, starting at about 75%. An R-500 conversion needs about 105% of the R-500 charge, starting at 100%. ART-36 does not recommend topping off a CFC system with Suva. Chemours’ MP66 bulletin says a system already on MP66 can be topped off after a leak, as long as you charge liquid.

Read the right column. Use the dew (vapor) column for superheat at suction pressure and the bubble (liquid) column for subcooling at liquid-line pressure. The superheat calculator uses the dew column; the temperature glide calculator shows the gap at any pressure. On a TXV system, charge by subcooling to the equipment or retrofit target with the subcooling calculator.

Expect the high side to run well above R-12. On this site’s tables, R-401B reads 39.8 psig at a 40°F dew point against 36.9 psig for R-12 at 40°F. At a 100°F bubble point it reads 152.0 psig against 116.9 psig for R-12. Do not charge to R-12 pressures.

Oil and compatibility

Sources differ on oil, so follow the compressor manufacturer:

  • BITZER lists mineral oil and alkylbenzene.
  • Chemours’ MP66 bulletin says it works with mineral oil and AB and needs no oil change on retrofit.
  • Copeland lists AB with mineral oil, or POE-32.
  • ART-36 says AB or POE can be used and existing mineral oil works in many close-coupled systems. For best oil return it suggests one oil change from mineral oil to AB, which removes 50-80% of the mineral oil.

Do not mix R-401B with R-12, R-500, R-401A or anything else. A mixture matches no PT chart. The refrigerant oil types guide compares the lubricants.

Safety, handling and recovery

R-401B is A1: lower toxicity, no flame propagation. It is an ozone-depleting refrigerant (ODP 0.040 from the 40 CFR 82 values for HCFC-22 and HCFC-124). Knowingly venting it is prohibited, recovery is required, and sales are restricted to certified technicians.

40 CFR 82.152 does not name R-401B, so its class comes from the 104°F liquid saturation pressure. This site’s table gives 161.5 psig (176.2 psia) at 104°F bubble, just over the 170 psia line, which makes it a high-pressure refrigerant by the definition. Small appliances (factory-sealed, 5 lb or less) need Type I certification, other equipment Type II; Universal covers both.

Appliance (made on or after Nov 15 1993) Required recovery
Small appliance 90% (compressor running), 80% (not running), or 4 in Hg
High-pressure, under 200 lb 0 in Hg
High-pressure, 200 lb or more 10 in Hg

Appliances with 50 lb or more fall under the ODS leak-repair rules in 40 CFR 82.157. Recovered R-401B cannot be sold to a new owner unless an EPA-certified reclaimer has reclaimed it.

Status and replacements

R-401B is regulated through its HCFCs. Since Jan 1 2010, HCFC-22 may be used as a refrigerant only in equipment made before that date, and its production and import ended Jan 1 2020. Since Jan 1 2020, newly produced HCFC-124 may be used only in equipment made before 2020, and HCFC-124 allowances fall to zero in 2030 (40 CFR 82.15). Supply is recovered, reclaimed or older stock.

No manufacturer or EPA document found names a dedicated successor for R-401B. Two HFC-based products list it among the refrigerants they replace:

  • R-437A (Freon MO49 Plus), which Chemours lists for R-12, R-401A, R-401B and R-409A systems.
  • R-450A (Solstice N13), which Honeywell’s application guide lists for R-401A, R-401B and R-409A.

Neither was designed for R-401B’s low-temperature niche, so confirm capacity and compressor approval first. The R-134a replacement guide covers the wider HFC and HFO options.

Common questions

What is the difference between R-401A and R-401B?

Same three components, different proportions. R-401B has 61% R-22 against 53% in R-401A, giving more capacity at low evaporator temperatures. DuPont aimed R-401B at low-temperature R-12 equipment and R-500 systems, and R-401A at general R-12 refrigeration.

How this chart was computed

Every pressure on this page is calculated, not copied: CoolProp 8.0.0 (HEOS backend), the open-source implementation of the reference equations of state, using the model custom:R22&R152A&R124:0.61,0.11,0.28 at the nominal ASHRAE 34 composition. Gauge values assume sea-level air pressure (14.696 psia); kPa values in the CSV are absolute.

Spot check against Forane Refrigerants Pressure Temperature Chart (Arkema, 2020):

°FColumnPublishedThis chartDifference
0bubble14.9 psig15.0 psig+0.1 psi
0dew9.20 psig9.01 psig-0.2 psi
40bubble50.1 psig50.1 psig+0.0 psi
40dew40.2 psig39.8 psig-0.4 psi
100bubble152.3 psig152.0 psig-0.3 psi
100dew134.7 psig133.6 psig-1.1 psi
0bubble15.1 psig15.0 psig-0.1 psi
0dew9.70 psig9.01 psig-0.7 psi
40bubble50.4 psig50.1 psig-0.3 psi
40dew41.1 psig39.8 psig-1.3 psi
100bubble153.0 psig152.0 psig-1.0 psi
100dew137.0 psig133.6 psig-3.4 psi

Custom model (CoolProp cannot load R401B.mix). Within 1.15 psi of Arkema (REFPROP 9.0) at every point. NRI's PT chart is 0.9-2.3 psi above Arkema on the dew side (137 vs 134.7 psig at 100 °F), so the 1.3 and 3.5 psi deviations from NRI reflect disagreement between the published sources more than the model (NRI's own psia table is 6 psi higher still). Treated as ok, as for R-401A.

Charts from different publishers can differ by a few tenths of a psi because of the equation of state and blend tolerances. Always charge to the equipment manufacturer's data. Full method and every spot check

Calculators for R-401B

Sources

  1. ASHRAE refrigerant designations (Standard 34) ashrae.org
  2. DuPont ART-36: Retrofit guidelines for Suva service refrigerants (distributor copy) wizard.youngsupply.com
  3. Chemours Freon MP66 technical bulletin (Brazil, 2021) pages.chemours.com
  4. Copeland AE Bulletin 93-11: Refrigerants and lubricants approved for Copeland compressors webapps.copeland.com
  5. BITZER Refrigerant Report (A-500/501) refrigerant data table bitzer.de
  6. EPA SNAP: Substitutes in household refrigerators and freezers epa.gov
  7. eCFR 40 CFR 82.15: Class II (HCFC) prohibitions ecfr.gov
  8. eCFR 40 CFR 82.152: Section 608 definitions (pressure classes) ecfr.gov

Reviewed . Found an error? Tell us and we will correct it.

More in Automotive, domestic and medium-temperature