R-450A PT Chart and Refrigerant Profile
R-450A is an A1 HFC/HFO blend zeotropic blend of R-134a and R-1234ze(E) (42/58 % by mass). At 40°F its vapor (dew) pressure is 28.9 psig; at 100°F its liquid (bubble) pressure is 109.3 psig.
Reviewed · PT values computed with CoolProp 8.0.0 and checked against a published chart (largest difference 1.0 psi)
R-450A at a glance
| Safety class (ASHRAE 34) | A1: lower toxicity, no flame propagation |
|---|---|
| Type | HFC/HFO blend, zeotropic blend |
| Composition | R-134a 42% · R-1234ze(E) 58% by mass |
| GWP (100-year, AR4) | 604 · AR5: 547AR4 sum uses 6 for R-1234ze(E). EPA's 40 CFR 84.64 value is 601.2. |
| Ozone depletion potential | 0 |
| Lubricant | POE (PVE also listed by BITZER) |
| Boiling point at 14.7 psia | -10.5°F bubble · -9.5°F dew |
| Critical point | 221.7°F, 565 psia |
| 40°F evaporating | 28.9 psig (dew), glide 1.1°F |
| 100°F condensing | 109.3 psig (bubble), glide 1.1°F |
| Charge as | Liquid only (blend can fractionate as vapor) |
| Typical use | Medium-temperature commercial refrigeration, new and retrofit; Vending and beverage dispensers; Chillers and heat pumps; High stage of CO2 cascade systems |
| Trade names | Solstice N13 (Honeywell, now Solstice Advanced Materials) |
| US status | HFC/HFO blend under the AIM Act phasedown; EPA-basis GWP 601.2 is below the 700 limit for new chillers but above the 150/300 limits for self-contained commercial and household refrigeration. |
| Replaces | R-134a, R-12, R-401A, R-401B, R-409A |
R-450A PT chart (°F and psig)
R-450A is a blend, so it has two saturation pressures at each temperature. Read the vapor (dew) column against suction pressure for superheat and the liquid (bubble) column against liquid-line pressure for subcooling. Tap a row to load it into the lookup.
-40°F to 150°F · psig at sea level · °C and kPa in the CSV · italic = inches Hg vacuum
| °F | Liquidbubble psig | Vapordew psig |
|---|---|---|
| -40 | 16.4″ | 16.8″ |
| -39 | 16.0″ | 16.4″ |
| -38 | 15.6″ | 16.0″ |
| -37 | 15.1″ | 15.6″ |
| -36 | 14.7″ | 15.1″ |
| -35 | 14.3″ | 14.7″ |
| -34 | 13.8″ | 14.3″ |
| -33 | 13.4″ | 13.8″ |
| -32 | 12.9″ | 13.4″ |
| -31 | 12.4″ | 12.9″ |
| -30 | 11.9″ | 12.4″ |
| -29 | 11.4″ | 12.0″ |
| -28 | 10.9″ | 11.4″ |
| -27 | 10.4″ | 10.9″ |
| -26 | 9.9″ | 10.4″ |
| -25 | 9.3″ | 9.9″ |
| -24 | 8.8″ | 9.3″ |
| -23 | 8.2″ | 8.8″ |
| -22 | 7.6″ | 8.2″ |
| -21 | 7.0″ | 7.6″ |
| -20 | 6.4″ | 7.0″ |
| -19 | 5.8″ | 6.4″ |
| -18 | 5.2″ | 5.8″ |
| -17 | 4.5″ | 5.2″ |
| -16 | 3.8″ | 4.5″ |
| -15 | 3.2″ | 3.9″ |
| -14 | 2.5″ | 3.2″ |
| -13 | 1.8″ | 2.5″ |
| -12 | 1.1″ | 1.8″ |
| -11 | 0.3″ | 1.1″ |
| -10 | 0.2 | 0.4″ |
| -9 | 0.6 | 0.2 |
| -8 | 1.0 | 0.6 |
| -7 | 1.3 | 0.9 |
| -6 | 1.7 | 1.3 |
| -5 | 2.1 | 1.7 |
| -4 | 2.5 | 2.1 |
| -3 | 3.0 | 2.5 |
| -2 | 3.4 | 2.9 |
| -1 | 3.8 | 3.4 |
| 0 | 4.3 | 3.8 |
| 1 | 4.7 | 4.2 |
| 2 | 5.2 | 4.7 |
| 3 | 5.6 | 5.1 |
| 4 | 6.1 | 5.6 |
| 5 | 6.6 | 6.1 |
| 6 | 7.1 | 6.6 |
| 7 | 7.6 | 7.0 |
| 8 | 8.1 | 7.5 |
| 9 | 8.6 | 8.1 |
| 10 | 9.1 | 8.6 |
| 11 | 9.7 | 9.1 |
| 12 | 10.2 | 9.6 |
| 13 | 10.8 | 10.2 |
| 14 | 11.3 | 10.7 |
| 15 | 11.9 | 11.3 |
| 16 | 12.5 | 11.9 |
| 17 | 13.1 | 12.5 |
| 18 | 13.7 | 13.1 |
| 19 | 14.3 | 13.7 |
| 20 | 15.0 | 14.3 |
| 21 | 15.6 | 14.9 |
| 22 | 16.2 | 15.5 |
| 23 | 16.9 | 16.2 |
| 24 | 17.6 | 16.8 |
| 25 | 18.2 | 17.5 |
| 26 | 18.9 | 18.2 |
| 27 | 19.6 | 18.9 |
| 28 | 20.3 | 19.6 |
| 29 | 21.1 | 20.3 |
| 30 | 21.8 | 21.0 |
| 31 | 22.5 | 21.7 |
| 32 | 23.3 | 22.5 |
| 33 | 24.1 | 23.2 |
| 34 | 24.9 | 24.0 |
| 35 | 25.6 | 24.8 |
| 36 | 26.5 | 25.6 |
| 37 | 27.3 | 26.4 |
| 38 | 28.1 | 27.2 |
| 39 | 28.9 | 28.0 |
| 40 | 29.8 | 28.9 |
| 41 | 30.7 | 29.7 |
| 42 | 31.6 | 30.6 |
| 43 | 32.4 | 31.5 |
| 44 | 33.4 | 32.4 |
| 45 | 34.3 | 33.3 |
| 46 | 35.2 | 34.2 |
| 47 | 36.2 | 35.1 |
| 48 | 37.1 | 36.1 |
| 49 | 38.1 | 37.0 |
| 50 | 39.1 | 38.0 |
| 51 | 40.1 | 39.0 |
| 52 | 41.1 | 40.0 |
| 53 | 42.1 | 41.0 |
| 54 | 43.2 | 42.0 |
| 55 | 44.2 | 43.1 |
| 56 | 45.3 | 44.1 |
| 57 | 46.4 | 45.2 |
| 58 | 47.5 | 46.3 |
| 59 | 48.6 | 47.4 |
| 60 | 49.8 | 48.5 |
| 61 | 50.9 | 49.6 |
| 62 | 52.1 | 50.8 |
| 63 | 53.3 | 52.0 |
| 64 | 54.5 | 53.1 |
| 65 | 55.7 | 54.3 |
| 66 | 56.9 | 55.6 |
| 67 | 58.2 | 56.8 |
| 68 | 59.4 | 58.0 |
| 69 | 60.7 | 59.3 |
| 70 | 62.0 | 60.6 |
| 71 | 63.3 | 61.9 |
| 72 | 64.7 | 63.2 |
| 73 | 66.0 | 64.5 |
| 74 | 67.4 | 65.8 |
| 75 | 68.7 | 67.2 |
| 76 | 70.1 | 68.6 |
| 77 | 71.6 | 70.0 |
| 78 | 73.0 | 71.4 |
| 79 | 74.4 | 72.8 |
| 80 | 75.9 | 74.3 |
| 81 | 77.4 | 75.8 |
| 82 | 78.9 | 77.2 |
| 83 | 80.4 | 78.7 |
| 84 | 82.0 | 80.3 |
| 85 | 83.5 | 81.8 |
| 86 | 85.1 | 83.4 |
| 87 | 86.7 | 85.0 |
| 88 | 88.3 | 86.6 |
| 89 | 90.0 | 88.2 |
| 90 | 91.6 | 89.8 |
| 91 | 93.3 | 91.5 |
| 92 | 95.0 | 93.1 |
| 93 | 96.7 | 94.8 |
| 94 | 98.5 | 96.6 |
| 95 | 100.2 | 98.3 |
| 96 | 102.0 | 100.1 |
| 97 | 103.8 | 101.8 |
| 98 | 105.6 | 103.6 |
| 99 | 107.5 | 105.4 |
| 100 | 109.3 | 107.3 |
| 101 | 111.2 | 109.1 |
| 102 | 113.1 | 111.0 |
| 103 | 115.0 | 112.9 |
| 104 | 117.0 | 114.9 |
| 105 | 119.0 | 116.8 |
| 106 | 120.9 | 118.8 |
| 107 | 123.0 | 120.8 |
| 108 | 125.0 | 122.8 |
| 109 | 127.0 | 124.8 |
| 110 | 129.1 | 126.9 |
| 111 | 131.2 | 129.0 |
| 112 | 133.4 | 131.1 |
| 113 | 135.5 | 133.2 |
| 114 | 137.7 | 135.3 |
| 115 | 139.9 | 137.5 |
| 116 | 142.1 | 139.7 |
| 117 | 144.3 | 141.9 |
| 118 | 146.6 | 144.2 |
| 119 | 148.9 | 146.4 |
| 120 | 151.2 | 148.7 |
| 121 | 153.5 | 151.1 |
| 122 | 155.9 | 153.4 |
| 123 | 158.3 | 155.8 |
| 124 | 160.7 | 158.2 |
| 125 | 163.1 | 160.6 |
| 126 | 165.6 | 163.0 |
| 127 | 168.1 | 165.5 |
| 128 | 170.6 | 168.0 |
| 129 | 173.2 | 170.5 |
| 130 | 175.7 | 173.0 |
| 131 | 178.3 | 175.6 |
| 132 | 180.9 | 178.2 |
| 133 | 183.6 | 180.8 |
| 134 | 186.2 | 183.5 |
| 135 | 188.9 | 186.2 |
| 136 | 191.7 | 188.9 |
| 137 | 194.4 | 191.6 |
| 138 | 197.2 | 194.4 |
| 139 | 200.0 | 197.2 |
| 140 | 202.8 | 200.0 |
| 141 | 205.7 | 202.8 |
| 142 | 208.6 | 205.7 |
| 143 | 211.5 | 208.6 |
| 144 | 214.5 | 211.5 |
| 145 | 217.4 | 214.5 |
| 146 | 220.5 | 217.5 |
| 147 | 223.5 | 220.5 |
| 148 | 226.6 | 223.5 |
| 149 | 229.6 | 226.6 |
| 150 | 232.8 | 229.7 |
Where you will find R-450A
R-450A is Honeywell’s Solstice N13, a blend of 42% R-134a and 58% R-1234ze(E). It is an A1 alternative to R-134a with less than half its GWP on the AR4 basis (604 against 1,430). Honeywell’s data sheet lists heat pumps, air- and water-cooled chillers, district heating and cooling, vending machines and beverage dispensers, the high stage of CO2 cascade systems and medium-temperature DX refrigeration.
EPA’s SNAP program listed it on Oct 21 2014 (79 FR 62863) as acceptable for new and retrofit use in supermarket, remote condensing, stand-alone and food processing equipment, transport, ice machines, water coolers, cold storage, industrial process refrigeration and AC, chillers and household refrigerators. Vending followed in 2015 and ice rinks in 2018. It is not on EPA’s list for residential and light commercial AC.
Sources disagree on what it replaced. BITZER lists R-134a and R-12. Honeywell’s application guide lists the HCFC service blends R-401A, R-401B and R-409A.
The legacy cylinder color assigned in AHRI Guideline N-2017 was sapphire blue; containers made since 2020 are light green-gray. Go by the label and the system tag.
Charging R-450A
R-450A has a small glide: 1.1°F at 40°F evaporating on this site’s table. It is still a blend, so charge liquid from the cylinder, metered slowly so it flashes before the compressor. Vapor charging can shift the blend.
No Honeywell charging guidance for R-450A was found. The retrofit guides labelled N13 on solstice.com download R-513A documents instead. Charge to the equipment maker’s instructions. For superheat, read suction pressure against the dew column with the superheat calculator. On TXV systems, charge by subcooling to the manufacturer’s target with the subcooling calculator, using the bubble column.
R-450A runs lower pressures than R-134a. On this site’s tables it reads 28.9 psig at a 40°F dew point against 35.1 psig for R-134a. At a 100°F bubble point it reads 109.3 psig against 124.2 psig for R-134a. A system converted from R-134a will show lower gauge readings at the same saturation temperatures, so do not charge to R-134a pressures. The PT chart guide explains bubble and dew columns.
Oil and compatibility
R-450A runs on synthetic oil. BITZER lists POE and PVE. Honeywell’s data sheet recommends POE and says to check with the compressor maker. Copeland lists POE-32 for medium- and high-temperature refrigeration only, with specific POE grades for some compressor families.
A system coming from R-134a on POE has the right oil family already; confirm the viscosity grade with the compressor maker. A system coming from R-12 or an HCFC blend on mineral oil or alkylbenzene needs the oil dealt with, because those oils are not on the R-450A lists above. See the refrigerant oil types guide.
Recover the old charge completely. Never top off R-134a with R-450A or the reverse.
Safety, handling and recovery
R-450A is A1 under ASHRAE 34: lower toxicity, no flame propagation, even though R-1234ze(E) alone is A2L. ODP is 0. It is a non-exempt substitute: venting is prohibited, required recovery levels apply, and since Jan 1 2018 sales are restricted to certified technicians.
It is a medium-pressure refrigerant under 40 CFR 82.152: this site’s table gives 117.0 psig (131.7 psia) at a 104°F bubble point, inside the 45-170 psia band. Small appliances need Type I certification, other equipment Type II; Universal covers both.
| Appliance (made on or after Nov 15 1993) | Required recovery |
|---|---|
| Small appliance | 90% (compressor running), 80% (not running), or 4 in Hg |
| Medium-pressure, under 200 lb | 10 in Hg |
| Medium-pressure, 200 lb or more | 15 in Hg |
From Jan 1 2026 the HFC leak-repair rule (40 CFR 84.106) applies to appliances with 15 lb or more of charge outside residential and light commercial AC.
Status and replacements
R-450A contains R-134a, so it falls under the AIM Act phasedown (40 CFR 84.7): allowances 60% of baseline in 2024-2028, 30% in 2029-2033, 20% in 2034-2035 and 15% from 2036. HFOs are not regulated substances, so only the R-134a share counts.
Under Technology Transitions, its EPA-basis GWP of 601.2 is below 700. That keeps it allowed in new comfort and process chillers, and in new cold storage, remote condensing units and supermarket systems until the 150/300 limits arrive on Jan 1 2032. It is above the 150/300 limits set for new household refrigerators, stand-alone retail equipment, vending machines and ice makers. Servicing existing equipment is legal. The AIM Act rules page covers the sector limits.
Availability is uncertain. N13 does not appear in the current Solstice Refrigerants Applications Chart, though its retrofit-guide links remain on solstice.com. No successor is named. Compare it with the alternatives in the R-134a replacement guide.
Common questions
R-450A vs R-134a: what changes?
R-450A has less than half the GWP of R-134a (604 against 1,430, AR4), uses POE like stationary R-134a systems, and runs lower pressures at the same temperature. It also has a 1°F glide, so charge liquid and read dew and bubble columns.
R-450A vs R-513A?
Both are A1 R-134a alternatives. R-513A runs at higher pressure: 39.8 psig at a 40°F dew point against 28.9 psig for R-450A on this site’s tables. R-513A is an azeotrope with almost no glide.
How this chart was computed
Every pressure on this page is calculated, not copied: CoolProp 8.0.0 (HEOS backend), the open-source implementation of the reference equations of state, using the model mix:R450A at the nominal ASHRAE 34 composition. Gauge values assume sea-level air pressure (14.696 psia); kPa values in the CSV are absolute.
Spot check against National Refrigerants Refrigerant Reference Guide, 7th Edition 2020: R-450A:
| °F | Column | Published | This chart | Difference |
|---|---|---|---|---|
| 0 | bubble | 18.7 psia | 19.0 psia | +0.3 psi |
| 0 | dew | 18.3 psia | 18.5 psia | +0.2 psi |
| 40 | bubble | 44.1 psia | 44.5 psia | +0.4 psi |
| 40 | dew | 43.1 psia | 43.6 psia | +0.5 psi |
| 100 | bubble | 123.2 psia | 124.0 psia | +0.8 psi |
| 100 | dew | 121.0 psia | 122.0 psia | +1.0 psi |
Within 1 psi (0.7%) of the NRI table; NRI's psig chart rounds to whole psi above 100 °F.
Charts from different publishers can differ by a few tenths of a psi because of the equation of state and blend tolerances. Always charge to the equipment manufacturer's data. Full method and every spot check
Calculators for R-450A
Sources
- ASHRAE refrigerant designations (Standard 34) ashrae.org
- UNEP/ASHRAE factsheet: refrigerant designations and safety classifications ashrae.org
- Honeywell Solstice N13 (R-450A) technical data sheet (archived) web.archive.org
- Honeywell Refrigerants Application Guide (BRO-23-02-EN) solstice.com
- BITZER Refrigerant Report (A-500/501) refrigerant data table bitzer.de
- Copeland AE Bulletin 93-11: Refrigerants and lubricants approved for Copeland compressors webapps.copeland.com
- Federal Register 79 FR 62863 (Oct 21 2014): SNAP listing including R-450A govinfo.gov
- eCFR 40 CFR 84.54: Technology Transitions restrictions by sector ecfr.gov
Reviewed . Found an error? Tell us and we will correct it.