R-421A PT Chart and Refrigerant Profile

R-421A is an A1 HFC zeotropic blend of R-125 and R-134a (58/42 % by mass). At 40°F its vapor (dew) pressure is 58.1 psig; at 100°F its liquid (bubble) pressure is 197.4 psig.

Reviewed · PT values computed with CoolProp 8.0.0 and checked against a published chart (largest difference 0.0 psi)

R-421A at a glance

Safety class (ASHRAE 34)A1: lower toxicity, no flame propagation
TypeHFC, zeotropic blend
CompositionR-125 58% · R-134a 42% by mass
GWP (100-year, AR4)2,631 · AR5: 2,385EPA AIM Act exchange value (AR4 basis) is 2,630.6
Ozone depletion potential0
LubricantMO, AB or POE (A-Gas); POE (BITZER)
Boiling point at 14.7 psia-41.2°F bubble · -31.6°F dew
Critical point181.0°F, 568 psia
40°F evaporating58.1 psig (dew), glide 7.6°F
100°F condensing197.4 psig (bubble), glide 5.6°F
Charge asLiquid only (blend can fractionate as vapor)
Typical useR-22 retrofit in residential and commercial AC; R-22 retrofit in medium- and high-temperature refrigeration
Trade namesChoice R421A (A-Gas)
US statusSNAP-acceptable R-22 substitute in residential and light commercial AC (2006); used to service existing systems, too high in GWP for new AC or refrigeration equipment.
ReplacesR-22

R-421A gauge reading to saturation temperature

psig

°F

ft

39.9°F vapor (dew) saturation at 58 psig: use for suction and superheat 32.3°F liquid (bubble) saturation: use for the liquid line and subcooling

Enter a vacuum as a negative psig (−5 psig ≈ 10.2 in Hg). Gauges read relative to local air pressure, so above about 2,000 ft the elevation correction changes low-pressure readings noticeably. PT calculator for all refrigerants

R-421A PT chart (°F and psig)

R-421A is a blend, so it has two saturation pressures at each temperature. Read the vapor (dew) column against suction pressure for superheat and the liquid (bubble) column against liquid-line pressure for subcooling. Tap a row to load it into the lookup.

-40°F to 150°F · psig at sea level · °C and kPa in the CSV · italic = inches Hg vacuum

R-421A pressure-temperature chart, -40°F to 150°F
°FLiquidbubble psigVapordew psig
-400.56.1″
-390.95.5″
-381.34.8″
-371.74.1″
-362.13.3″
-352.62.6″
-343.01.8″
-333.41.1″
-323.90.3″
-314.40.3
-304.80.7
-295.31.1
-285.81.5
-276.31.9
-266.82.4
-257.42.8
-247.93.3
-238.43.7
-229.04.2
-219.64.7
-2010.15.2
-1910.75.7
-1811.36.2
-1711.96.7
-1612.57.3
-1513.27.8
-1413.88.4
-1314.58.9
-1215.19.5
-1115.810.1
-1016.510.7
-917.211.3
-817.911.9
-718.612.6
-619.313.2
-520.113.9
-420.814.5
-321.615.2
-222.415.9
-123.216.6
024.017.3
124.818.1
225.618.8
326.519.6
427.420.3
528.221.1
629.121.9
730.022.7
830.923.6
931.924.4
1032.825.3
1133.826.1
1234.827.0
1335.827.9
1436.828.8
1537.829.7
1638.830.7
1739.931.6
1840.932.6
1942.033.6
2043.134.6
2144.235.6
2245.436.6
2346.537.7
2447.738.7
2548.939.8
2650.140.9
2751.342.0
2852.543.2
2953.844.3
3055.045.5
3156.346.7
3257.647.9
3359.049.1
3460.350.3
3561.751.6
3663.052.8
3764.454.1
3865.855.5
3967.356.8
4068.758.1
4170.259.5
4271.760.9
4373.262.3
4474.763.7
4576.365.2
4677.966.6
4779.468.1
4881.169.6
4982.771.1
5084.372.7
5186.074.3
5287.775.9
5389.477.5
5491.279.1
5592.980.8
5694.782.4
5796.584.1
5898.385.9
59100.287.6
60102.089.4
61103.991.2
62105.993.0
63107.894.8
64109.896.7
65111.798.5
66113.7100.5
67115.8102.4
68117.8104.3
69119.9106.3
70122.0108.3
71124.1110.4
72126.3112.4
73128.5114.5
74130.7116.6
75132.9118.7
76135.2120.9
77137.4123.1
78139.8125.3
79142.1127.5
80144.4129.8
81146.8132.1
82149.2134.4
83151.7136.7
84154.1139.1
85156.6141.5
86159.1143.9
87161.7146.4
88164.3148.9
89166.9151.4
90169.5153.9
91172.2156.5
92174.8159.1
93177.6161.7
94180.3164.4
95183.1167.1
96185.9169.8
97188.7172.6
98191.6175.3
99194.5178.1
100197.4181.0
101200.3183.9
102203.3186.8
103206.3189.7
104209.4192.7
105212.4195.7
106215.5198.7
107218.7201.8
108221.8204.9
109225.0208.0
110228.3211.2
111231.5214.4
112234.8217.7
113238.2220.9
114241.5224.3
115244.9227.6
116248.4231.0
117251.8234.4
118255.3237.9
119258.9241.3
120262.4244.9
121266.0248.4
122269.7252.0
123273.4255.7
124277.1259.3
125280.8263.1
126284.6266.8
127288.4270.6
128292.3274.4
129296.2278.3
130300.1282.2
131304.0286.2
132308.1290.2
133312.1294.2
134316.2298.3
135320.3302.4
136324.4306.6
137328.6310.8
138332.9315.0
139337.1319.3
140341.5323.6
141345.8328.0
142350.2332.4
143354.6336.9
144359.1341.4
145363.6346.0
146368.2350.6
147372.8355.2
148377.4359.9
149382.1364.7
150386.9369.5

Download the R-421A table as CSV

R-421A pressure-temperature curve from -40°F to 150°F, showing the bubble and dew lines
R-421A saturation pressure against temperature; the gap between the liquid and vapor lines is the glide.

Where you will find R-421A

R-421A is an R-22 service blend. You find it in R-22 air conditioners, heat pumps and medium- or high-temperature refrigeration that were recharged with it instead of R-22, not in equipment designed for it. A-Gas sells it as Choice R421A and lists residential and commercial AC and commercial and industrial refrigeration as uses, with performance temperature ranges comparable with R-22 (A-Gas).

The nameplate on these systems still says R-22, so the retrofit label is your only clue. If there is no label and the pressures do not match R-22 at the measured temperatures, assume an unknown blend and recover it rather than topping off.

R-421A is a two-part HFC blend of R-125 and R-134a (58/42 by mass). It contains no R-22 and no ozone-depleting component. New cylinders are light green-gray (RAL 7044) like every refrigerant, so go by the label.

Charging R-421A

Charge liquid only. R-421A is a zeotropic blend, and vapor drawn from the cylinder does not have the same composition as the liquid. Meter the liquid into the suction side slowly with the system running.

R-421A does not read like R-22 on the gauges. At 40°F, R-22 saturates at 68.6 psig. R-421A at 40°F shows 58.1 psig on the dew column and 68.7 psig on the bubble column, a glide of about 7.6°F. If you read an R-421A system with an R-22 scale, the suction saturation temperature comes out wrong and so does superheat. Set your manifold or digital gauge to R-421A, or use the gauge lookup on this page.

  • Superheat: convert suction pressure with the dew column. On fixed-orifice systems, charge to target superheat from CEC Title 24 Table RA3.2-2 (installer tolerance ±5°F, valid at 55–115°F outdoor, return dry bulb of 70°F or more, return wet bulb of 76°F or less) with the target superheat calculator.
  • Subcooling: convert liquid-line pressure with the bubble column, then compare it with the manufacturer’s subcooling target for TXV systems using the subcooling calculator.

The temperature glide calculator gives the glide at any pressure. A-Gas’s product page gives no starting charge percentage, so add charge by weight in small steps and finish to superheat or subcooling. The OEM targets were set for R-22 and the blend supplier’s retrofit instructions take precedence.

Do not top off an R-22 system with R-421A or mix the two. Recover all R-22 first, then charge R-421A into the evacuated system.

Oil and compatibility

Sources differ on oil. A-Gas lists R-421A as compatible with mineral oil (MO), alkylbenzene (AB) and POE (A-Gas), which is why it is sold as a retrofit that can keep the existing oil. BITZER’s refrigerant data table lists POE only for R-421A (BITZER).

In practice, check the compressor maker’s approval for R-421A with the oil already in the system. Replace the filter-drier, label the system with the refrigerant and oil, and evacuate to the OEM target, typically 350–500 microns (evacuation guide). See the refrigerant oil guide.

Safety, handling and recovery

R-421A is ASHRAE class A1: lower toxicity and no flame propagation. It runs in the same pressure range as R-22, so R-22-rated gauges, hoses and recovery cylinders are suitable.

Section 608 Type II (or Universal) certification covers R-421A systems, and since Jan 1 2018 only certified technicians may buy it. By the 40 CFR 82.152 definition it is a high-pressure refrigerant: its computed liquid saturation pressure at 104°F is 224.1 psia (209.4 psig, bubble). Recover appliances under 200 lb to 0 in Hg, and those of 200 lb or more to 10 in Hg.

Recover R-421A into its own labeled recovery cylinder (gray with a yellow top), never into a tank that already holds R-22 or another blend.

Status and replacements

EPA’s SNAP program listed R-421A as an acceptable R-22 substitute in residential and light commercial AC on Sept 28 2006 (EPA SNAP). Using it to service and retrofit existing R-22 systems remains legal.

It is all HFC, with a GWP of 2,631 (AR4), higher than both R-22 (1,810) and R-410A (2,088). That has two consequences:

  • Supply: every pound counts against the AIM Act HFC phasedown, which steps allowances down to 60% of baseline in 2024–2028, 30% in 2029–2033, 20% in 2034–2035 and 15% from 2036.
  • New equipment: under the Technology Transitions rule (40 CFR 84.54) its GWP is far above the limits for new AC, heat pumps and commercial refrigeration. R-421A is also named as restricted in new road and marine transport refrigeration from Jan 1 2025.

For a long-term fix, replacing the R-22 equipment is the alternative to a retrofit. Other R-22 retrofit blends include R-422B, R-422D, R-438A, R-427A, R-417A and R-407C. Compare them in R-22 replacement refrigerants, and see the R-22 phase-out guide.

Common questions

Is R-421A a drop-in replacement for R-22?

It is sold as one that can run with the existing oil (A-Gas), but it is not identical to R-22. Its dew-point pressures are lower than R-22’s at the same temperature, it has glide, and it must be charged as liquid.

What oil does R-421A use?

A-Gas lists mineral oil, AB and POE as compatible; BITZER lists POE. Confirm with the compressor maker.

How this chart was computed

Every pressure on this page is calculated, not copied: CoolProp 8.0.0 (HEOS backend), the open-source implementation of the reference equations of state, using the model mix:R421A at the nominal ASHRAE 34 composition. Gauge values assume sea-level air pressure (14.696 psia); kPa values in the CSV are absolute.

Spot check against Choice Refrigerants R-421A PT Chart (liquid / vapor phase pressure):

°FColumnPublishedThis chartDifference
0bubble24.0 psig24.0 psig-0.0 psi
0dew17.3 psig17.3 psig+0.0 psi
40bubble68.7 psig68.7 psig+0.0 psi
40dew58.1 psig58.1 psig+0.0 psi
100bubble197.4 psig197.4 psig-0.0 psi
100dew181.0 psig181.0 psig-0.0 psi

Charts from different publishers can differ by a few tenths of a psi because of the equation of state and blend tolerances. Always charge to the equipment manufacturer's data. Full method and every spot check

Comparisons with R-421A

Calculators for R-421A

Sources

  1. A-Gas: Choice R421A product page agas.com
  2. BITZER Refrigerant Report (A-500/501) refrigerant data table bitzer.de
  3. EPA SNAP: Substitutes in residential and light commercial AC and heat pumps epa.gov
  4. ASHRAE Refrigerant Designations ashrae.org
  5. 40 CFR 84.54 - Technology Transitions restrictions by sector ecfr.gov
  6. 40 CFR 82.152 - Section 608 definitions and pressure classes ecfr.gov

Reviewed . Found an error? Tell us and we will correct it.