R-424A (RS-44) PT Chart and Refrigerant Profile

R-424A (RS-44) is an A1 HFC/HC zeotropic blend of R-125, R-134a, R-600a, R-600 and R-601a (50.5/47/0.9/1/0.6 % by mass). At 40°F its vapor (dew) pressure is 55.1 psig; at 100°F its liquid (bubble) pressure is 189.2 psig.

Reviewed · PT values computed with CoolProp 8.0.0 and checked against a published chart (largest difference 0.6 psi)

R-424A at a glance

Safety class (ASHRAE 34)A1: lower toxicity, no flame propagation
TypeHFC/HC, zeotropic blend
CompositionR-125 50.5% · R-134a 47% · R-600a 0.9% · R-600 1% · R-601a 0.6% by mass
GWP (100-year, AR4)2,440 · AR5: 2,212EPA's 40 CFR 84.64 calculation gives 2,439.6 (isopentane excluded). EPA lists a separate RS-44 (2003 formulation) at 2,420.
Ozone depletion potential0
LubricantMineral oil, AB or POE (some systems need POE)
Boiling point at 14.7 psia-39.7°F bubble · -29.9°F dew
Critical point184.2°F, 566 psia
40°F evaporating55.1 psig (dew), glide 7.8°F
100°F condensing189.2 psig (bubble), glide 5.7°F
Charge asLiquid only (blend can fractionate as vapor)
Typical useR-22 retrofit in commercial and residential DX air conditioning; Medium- and high-temperature commercial refrigeration; Transport refrigeration
Trade namesRS-44 (Refrigerant Solutions Ltd; marketed by A-Gas)
US statusRetrofit and service refrigerant only; its GWP of about 2,440 is above all 40 CFR 84.54 limits for new equipment. A-Gas Canada calls RS-44 a legacy product.
ReplacesR-22

R-424A gauge reading to saturation temperature

psig

°F

ft

40.0°F vapor (dew) saturation at 55 psig: use for suction and superheat 32.2°F liquid (bubble) saturation: use for the liquid line and subcooling

Enter a vacuum as a negative psig (−5 psig ≈ 10.2 in Hg). Gauges read relative to local air pressure, so above about 2,000 ft the elevation correction changes low-pressure readings noticeably. PT calculator for all refrigerants

R-424A PT chart (°F and psig)

R-424A is a blend, so it has two saturation pressures at each temperature. Read the vapor (dew) column against suction pressure for superheat and the liquid (bubble) column against liquid-line pressure for subcooling. Tap a row to load it into the lookup.

-40°F to 150°F · psig at sea level · °C and kPa in the CSV · italic = inches Hg vacuum

R-424A pressure-temperature chart, -40°F to 150°F
°FLiquidbubble psigVapordew psig
-400.2″7.2″
-390.36.6″
-380.75.9″
-371.15.2″
-361.54.5″
-351.93.8″
-342.33.1″
-332.72.4″
-323.21.6″
-313.60.8″
-304.10.0″
-294.50.4
-285.00.8
-275.51.2
-266.01.6
-256.52.0
-247.02.5
-237.52.9
-228.13.4
-218.63.8
-209.24.3
-199.74.8
-1810.35.3
-1710.95.8
-1611.56.3
-1512.16.8
-1412.77.4
-1313.37.9
-1213.98.5
-1114.69.0
-1015.29.6
-915.910.2
-816.610.8
-717.311.4
-618.012.0
-518.712.6
-419.413.3
-320.213.9
-220.914.6
-121.715.3
022.516.0
123.316.7
224.117.4
324.918.1
425.718.8
526.519.6
627.420.3
728.321.1
829.121.9
930.022.7
1031.023.5
1131.924.4
1232.825.2
1333.826.1
1434.726.9
1535.727.8
1636.728.7
1737.729.6
1838.830.6
1939.831.5
2040.932.5
2141.933.4
2243.034.4
2344.135.4
2445.236.5
2546.437.5
2647.538.5
2748.739.6
2849.940.7
2951.141.8
3052.342.9
3153.544.1
3254.845.2
3356.146.4
3457.447.6
3558.748.8
3660.050.0
3761.351.2
3862.752.5
3964.153.8
4065.555.1
4166.956.4
4268.357.7
4369.859.0
4471.260.4
4572.761.8
4674.263.2
4775.864.6
4877.366.1
4978.967.5
5080.569.0
5182.170.5
5283.772.1
5385.473.6
5487.075.2
5588.776.8
5690.478.4
5792.280.0
5893.981.7
5995.783.3
6097.585.0
6199.386.7
62101.288.5
63103.090.2
64104.992.0
65106.893.8
66108.895.7
67110.797.5
68112.799.4
69114.7101.3
70116.7103.2
71118.8105.2
72120.8107.1
73122.9109.1
74125.1111.2
75127.2113.2
76129.4115.3
77131.6117.4
78133.8119.5
79136.0121.6
80138.3123.8
81140.6126.0
82142.9128.2
83145.3130.5
84147.6132.8
85150.0135.1
86152.5137.4
87154.9139.8
88157.4142.1
89159.9144.5
90162.4147.0
91165.0149.5
92167.6152.0
93170.2154.5
94172.8157.0
95175.5159.6
96178.2162.2
97180.9164.9
98183.7167.5
99186.4170.2
100189.2173.0
101192.1175.7
102195.0178.5
103197.9181.3
104200.8184.2
105203.8187.1
106206.7190.0
107209.8192.9
108212.8195.9
109215.9198.9
110219.0202.0
111222.2205.1
112225.3208.2
113228.5211.3
114231.8214.5
115235.0217.7
116238.3220.9
117241.7224.2
118245.1227.5
119248.5230.9
120251.9234.3
121255.4237.7
122258.9241.2
123262.4244.6
124266.0248.2
125269.6251.7
126273.2255.3
127276.9259.0
128280.6262.7
129284.3266.4
130288.1270.1
131291.9273.9
132295.8277.7
133299.7281.6
134303.6285.5
135307.6289.5
136311.6293.5
137315.6297.5
138319.7301.6
139323.8305.7
140327.9309.8
141332.1314.0
142336.4318.3
143340.6322.6
144344.9326.9
145349.3331.3
146353.7335.7
147358.1340.1
148362.6344.6
149367.1349.2
150371.6353.8

Download the R-424A table as CSV

R-424A pressure-temperature curve from -40°F to 150°F, showing the bubble and dew lines
R-424A saturation pressure against temperature; the gap between the liquid and vapor lines is the glide.

Where you will find R-424A

R-424A is RS-44, a no-oil-change R-22 retrofit blend made by Refrigerant Solutions Ltd in the UK. ACHR News reported its US launch in 2007 through ComStar International, which imported it from RSL. A-Gas now markets RS-44 in the UK and Canada, and lists it for medium- and high-temperature AC and refrigeration: commercial AC, commercial refrigeration and transport units (A-Gas UK).

You will find it in R-22 split systems, rooftops and condensing units converted since its 2006 SNAP listing. The nameplate still says R-22, so read the retrofit label. Guideline N-2017 Table 1 assigns R-424A black, with no PMS number; on cylinders made since 2020 that color appears only on the label.

It is one of several five-component R-22 drop-ins with small hydrocarbon additions. R-438A (MO99) and R-453A (RS-70) are relatives with different mixes, so never read one chart for another.

Charging R-424A

Charge from the liquid phase. A-Gas UK says it must be charged as liquid. The Gasco FAQ adds that vapor charging is acceptable only if the whole cylinder goes into the system, because the cylinder’s vapor and liquid differ in composition.

This blend has real glide: 7.8°F at a 40°F dew point and 5.7°F at a 100°F bubble point. Use the columns correctly:

  • Superheat: suction pressure against the dew column. At 40°F this chart gives 55.1 psig dew and 65.5 psig bubble; reading the bubble column would make the superheat look several degrees higher than it is. Fixed orifices go by target superheat.
  • Subcooling: liquid-line pressure against the bubble column. TXV and EEV systems go by the manufacturer’s subcooling target.

Compared with R-22 (68.6 psig at 40°F), suction pressure at the same evaporator dew point is lower. Head pressure is close: 189.2 psig bubble at 100°F against 195.9 psig for R-22.

For a conversion, A-Gas’s general retrofit guide puts the initial charge at 90–95% by weight of the original R-22 charge. Add from there to the equipment’s targets. The temperature glide calculator shows the gap at any pressure.

Oil and compatibility

Sources agree it runs with the existing oil in most systems, but not all:

  • A-Gas Canada: compatible with existing oils, no hardware changes.
  • A-Gas UK: generally compatible with mineral oil, but conversion to POE may be needed in some cases; check with the compressor maker.
  • Gasco: mineral oil, AB or POE; a partial POE addition, about 25%, may be needed with long or complex piping, large receivers or very low evaporating temperatures.

Replace the filter-drier and evacuate to the OEM target before charging (evacuation guide). See the refrigerant oil guide.

Safety, handling and recovery

R-424A is A1 (lower toxicity, no flame propagation) per A-Gas, Gasco and EPA. The hydrocarbon content totals 2.5%.

It is a Section 608 high-pressure refrigerant: its computed liquid saturation pressure at 104°F is 215.5 psia (200.8 psig, bubble). Type II or Universal certification covers it, and sales have been limited to certified technicians since Jan 1 2018. Recover appliances made after Nov 15 1993 to 0 in Hg under 200 lb of charge and 10 in Hg at 200 lb or more (refrigerant recovery). Keep it in its own recovery cylinder, labeled R-424A.

Status and replacements

EPA SNAP lists R-424A as acceptable, retrofit and new, since Sept 28 2006 in residential and light commercial AC, industrial process AC and refrigeration, remote condensing units, supermarket systems, refrigerated transport, ice machines, ice rinks and dehumidifiers. In new centrifugal and positive-displacement chillers it has been unacceptable since Jan 1 2024, except under a narrowed use limit.

Its AR4 GWP of about 2,440 is above every Technology Transitions limit for new equipment, and 40 CFR 84.54 names it, and separately “RS-44 (2003 formulation)”, for new refrigerated transport from Jan 1 2025. Servicing and retrofitting existing equipment remain legal. HFC supply falls to 30% of baseline in 2029–2033 under the AIM Act.

Availability is the practical problem. A-Gas Canada calls RS-44 a legacy product being replaced by RS-70. A 2026 ChemPoint page for ComStar lists RS-44b (R-453A) rather than RS-44. We could not confirm a current US distributor. For other routes off R-22, see R-22 replacement options and R-22 vs MO99.

Common questions

Is R-424A a drop-in for R-22?

It is sold as a no-oil-change R-22 retrofit, and EPA accepts it for retrofitting R-22 AC. A-Gas UK still says some systems may need POE, and the charge is weighed in fresh after recovering the R-22.

What replaced RS-44?

A-Gas Canada says RS-44 is being replaced by RS-70. In the US, the RS-44b name belongs to R-453A.

How this chart was computed

Every pressure on this page is calculated, not copied: CoolProp 8.0.0 (HEOS backend), the open-source implementation of the reference equations of state, using the model custom:R125&R134a&IsoButane&n-Butane&Isopentane:0.505,0.47,0.009,0.01,0.006 at the nominal ASHRAE 34 composition. Gauge values assume sea-level air pressure (14.696 psia); kPa values in the CSV are absolute.

Spot check against RS-44 (R424A) Pressure & Temperature Table: Absolute, Refrigerant Solutions Ltd (undated):

°FColumnPublishedThis chartDifference
-0.4bubble36.7 psia36.8 psia+0.1 psi
-0.4dew30.3 psia30.4 psia+0.1 psi
39.2bubble78.8 psia79.0 psia+0.2 psi
39.2dew68.5 psia68.7 psia+0.2 psi
100.4bubble204.6 psia205.1 psia+0.5 psi
100.4dew188.2 psia188.8 psia+0.6 psi

Custom model with surrogate HFC/isopentane parameters; within 0.6 psi of the RSL table (RS-44 is RSL's name for R-424A). Compared at the printed °C points.

Charts from different publishers can differ by a few tenths of a psi because of the equation of state and blend tolerances. Always charge to the equipment manufacturer's data. Full method and every spot check

Calculators for R-424A

Sources

  1. A-Gas UK: R424A (RS-44) agas.com
  2. A-Gas Canada: RS-44 (R424A) agas.com
  3. Gasco: R-424A (RS-44) technical sheet and FAQ (French) gasco-france.com
  4. A-Gas UK: retrofit guide (general) agas.com
  5. ACHR News (Jan 2007): Four new refrigerants enter U.S. market achrnews.com
  6. EPA SNAP: Substitutes in residential and light commercial AC and heat pumps epa.gov
  7. EPA SNAP: Substitutes in centrifugal chillers epa.gov
  8. 40 CFR 84.54: Technology Transitions restrictions by sector ecfr.gov

Reviewed . Found an error? Tell us and we will correct it.